Plan Review Notes
Plan Review Notes For Permit 14110345
Permit Number 14110345
Review Stop P
Sequence Number 4
Notes
Date Text
2015-03-06 13:14:191) SHT. A2.2 - ELEVATION DETAILS #4 & 6 - THE GRAB BARS
 ARE TO BE MEASUERD TO THE TOP OF THE GRIPPING SURFACE
 FROM THE FLOOR, NOT TO THE CENTERLINE AS SHOWN. 2010
 FAC SEC.609.4.
 2) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE ZOELLER
 PUMP. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 3) SHT. P3.1 - THE MOP SINK (P-11) IS NOT SHOWN ON THE
 WATER RISER.CLARIFY.
 4) SHT.P3.1 - RISER #1 - SHOWS THE ICE MACHINE AND
 COOLER DISCHARGING TO THE GREASY WASTE SYSTEM. WASTES
 THAT DO NOT REQUIRE TREATMENT OR SEPARATION SHALL NOT
 DISCHARGE INTO ANY INTERCEPTOR OR SEPARATOR PER THE
 2010 FPC SEC.1003.2.
 5) SHT.P4.1 - DETAIL #10 - THE DETAIL FOR THE GREASE
 INTERCEPTOR IS NOT FOR A SCHIER TANK. DELETE THIS
 SPECIFICATION FROM THE PLANS AND INCLUDE THE SUBMITTED
 SPECIFICATION FOR THE SCHIER INTERCEPTOR ON THE PLANS
 OR SUBMIT 2 COPIES OF THE SPEC FOR THE SCHIER TANK.ONLY
 ONE COPY WAS SUBMITTED.
 6) THE CALCULATIONS FOR THE SIZING OF THE SCHIER
 INTERCEPTOR DO NOT APPEAR TO BE IN COMPLIANCE WITH THE
 METHOD RECOMMENDED BY SCHIER SCHIER RECOMMENDS THAT THE
 DRAINAGE SYSTEM FLOW RATE BE DETERMINED BY THE SIZE OF
 THE INTERCEPTOR'S INLET PIPE (STEP #1).
 THEN CALCULATE GREASE CAPACITY AFTER SIZING FOR FLOW
 RATE. I DO NOT SEE THE FLOW RATE CALCULATIONS ON SHT.
 P1.1. THE DAYS FOR PUMP OUT CYCLE IN SCHIER'S CATALOG
 IS 30, 60 & 90. THERE IS NO 45 DAY PUMP OUT CYCLE.
 CLARIFY.
 7) THE CALCULATIONS FOR THE SIZING OF THE SCIER
 INTERCEPTOR SHOULD BE VERIFIED BY A SCHIER
 REPRESENTATIVE TO CONFIRM THE SIZING IS CORRECT. YOU
 CAN CONTACT THE REPRESENTATIVE AT 1-800-538-4792.
 8) PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL BE
 CONNECTED IN ACCORDANCE WITH THE 2010 FPC
 SEC.712.3.5.PROVIDE A DETAIL AS TO HOW THE PUMP
 DISCHARGE LINE IS CONNECTED TO THE SANITARY SYSTEM OR
 REFER TO THIS CODE SECTION ON THE PLAN.
 9) THE HYDRO-MECHANICAL INTERCEPTORS FROM SCHIER HAVE
 FLOW CONTROLS THAT MUST BE VENTED IN ACCORDANCE WITH
 2010 FPC SEC.1003.3.4.2. EACH INTERCEPTOR SHALL BE
 EQUIPPED WITH A VENT FOR THE FLOW CONTROLS. SHOW THE
 LOCATION AND SIZE OF THE VENTS ON SHT.P1.1 AND ON THE
 SSANITARY RISER ON SHT.P3.1. THE FLOW CONTROL DEVICE
 SHALL BE VENTED AND TERMINATE NOT LESS THAN SIX (6)
 INCHES ABOVE THE FLOOD RIM LEVEL OR BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS PER THE
 2010 FPC SEC;1003.3.4.2.
 10) SUMP VENT SHALL RISE VERTICALLY A MINIMUM OF 6
 INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR
 TRAPPED FIXTURE BEING VENTED PRIOR TO OFFSETTING PER
 2010 FPC SEC.905.4, 905.5.
 11) THE LOCATION OF THE CHECK VALVE AND FULL OPEN VALVE
 FOR THE SUMP PUMP SHALL BE LOCATED ABOVE THE SUMP COVER
 OR UNDERGROUND OUTSIDE OF THE SUMP PIT AS REQUIRED PER
 THE 2010 FPC SEC.712.2,
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  