| Plan Review Notes For Permit 14110345 |
| Permit Number |
14110345 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-02-07 03:41:34 | 1) SHT.P1.1 -GREASE INTERCEPTOR SIZING CALCULATIONS - | | | THE GREASE INTERCEPTOR SIZING CALCULATIONS SHOW A | | | CAPACITY REQUIREMENT OF 2100 GALLONS. SHOW THE SIZE OF | | | THE EXISTING GREASE INTERCEPTOR(S) ON THE PLANS TO | | | CONFIRM THAT THE EXISTING INTERCEPTOR(S) HAVE THE | | | CAPACITY TO SEPARATE THE THE GREASY WASTE AND FUNCTION | | | IN THE MANNER DESIGNED TO ELIMINATE GREASE INTO THE | | | SANITARY SYSTEM. SIZE OF GREASE INTERCEPTORS SHALL | | | COMPLY WITH THE 2010 FBC-PLUMBING SECS.1003.1, | | | 1003.5.1.NOTE: THE MAXIMUM VOLUME OF AN INDIVIDUAL | | | GREASE INTERCEPTOR CHAMBER SHALL BE 1,250 GALLONS. WHEN | | | THE REQUIRED EFFECTIVE CAPACITY OF THE GREASE | | | INTERCEPTOR IS GREATER THAN 1250 GALLONS, INSTALLATION | | | OF MULTI - CHAMBERED GREASE INTERCEPTORS OR GREASE | | | INTERCEPTORS IN SERIES IS REQUIRED. 3RD REQUEST, | | | 2) IDENTIFY ON THE PLANS THE LOCATION OF THE EXISTING | | | GREASE INTERCEPTORS. THIS INFORMATION MAY BE OBTAINED | | | FROM CITY PLACE ADMINISTRATION OR YOU CAN CONTACT | | | SANDRA FELICIANO IN THE CITY OF WPB UTILITIES DEPT. WHO | | | MAY HAVE SOME INFORMATION. MS. FELICIANO'S PHONE NUMBER | | | IS 561-822-2171. | | | 3) INDICATE THE TYPE OF THE EXISTING INTERCEPTOR(S) ARE | | | THEY THE CONCRETE VAULT TYPE OR HYDROMECHANICAL? IF | | | HYDROMECHANICAL THEN THE SIZING EQUATION IN TABLE | | | 1003.5.1 CANNOT BE USED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|