Plan Review Notes
Plan Review Notes For Permit 14110345
Permit Number 14110345
Review Stop P
Sequence Number 3
Notes
Date Text
2015-02-07 03:41:341) SHT.P1.1 -GREASE INTERCEPTOR SIZING CALCULATIONS -
 THE GREASE INTERCEPTOR SIZING CALCULATIONS SHOW A
 CAPACITY REQUIREMENT OF 2100 GALLONS. SHOW THE SIZE OF
 THE EXISTING GREASE INTERCEPTOR(S) ON THE PLANS TO
 CONFIRM THAT THE EXISTING INTERCEPTOR(S) HAVE THE
 CAPACITY TO SEPARATE THE THE GREASY WASTE AND FUNCTION
 IN THE MANNER DESIGNED TO ELIMINATE GREASE INTO THE
 SANITARY SYSTEM. SIZE OF GREASE INTERCEPTORS SHALL
 COMPLY WITH THE 2010 FBC-PLUMBING SECS.1003.1,
 1003.5.1.NOTE: THE MAXIMUM VOLUME OF AN INDIVIDUAL
 GREASE INTERCEPTOR CHAMBER SHALL BE 1,250 GALLONS. WHEN
 THE REQUIRED EFFECTIVE CAPACITY OF THE GREASE
 INTERCEPTOR IS GREATER THAN 1250 GALLONS, INSTALLATION
 OF MULTI - CHAMBERED GREASE INTERCEPTORS OR GREASE
 INTERCEPTORS IN SERIES IS REQUIRED. 3RD REQUEST,
 2) IDENTIFY ON THE PLANS THE LOCATION OF THE EXISTING
 GREASE INTERCEPTORS. THIS INFORMATION MAY BE OBTAINED
 FROM CITY PLACE ADMINISTRATION OR YOU CAN CONTACT
 SANDRA FELICIANO IN THE CITY OF WPB UTILITIES DEPT. WHO
 MAY HAVE SOME INFORMATION. MS. FELICIANO'S PHONE NUMBER
 IS 561-822-2171.
 3) INDICATE THE TYPE OF THE EXISTING INTERCEPTOR(S) ARE
 THEY THE CONCRETE VAULT TYPE OR HYDROMECHANICAL? IF
 HYDROMECHANICAL THEN THE SIZING EQUATION IN TABLE
 1003.5.1 CANNOT BE USED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  