| Plan Review Notes For Permit 14110345 |
| Permit Number |
14110345 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-01-17 11:22:26 | 1) THE GREASE INTERCEPTOR SIZING CALCULATIONS ON | | | SHT.P1.1 SHOW A CAPACITY REQUIREMENT OF 2100 GALLONS. | | | SHOW THE SIZE OF THE EXISTING GREASE INTERCEPTOR(S) ON | | | THE PLANS TO CONFIRM THE EXISTING GREASY WASTE SYSTEM | | | IS ADEQUATE FOR THIS RESTAURANT. NOTE: THE MAXIMUM | | | CAPACITY OF A SINGLE GREASE INTERCEPTOR IS 1250 GALS. | | | WPB AMEND. TO 2010 FBC SEC. 107.2.1. & 2010 FPC | | | SEC.1003.5.1. | | | 2) THE REVISED SHEETS SHALL BE INSERTED INTO THE | | | EXISTING SET TO MAKE 2 COMPLETE SETS OF PLANS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|