| Date |
Text |
| 2014-11-22 11:32:55 | 1)SUBMIT THE CORRECT OCCUPANT LOAD FOR THE SPACE. SHT. |
| | A2.0 SHOWS THREE DIFFERENT NUMBERS (248, 236, 172 ). |
| | THE MINIMUM SANITARY FACILITIES WILL BE BASED ON THE |
| | CORRECT OCCUPANT LOAD. |
| | 2) SHT. A2.2 - ELEVS. #4 & # 8 - SUBMIT ELEVATIONS |
| | WHERE THE DIMENSIONS CAN BE CLEARLY READ. WPB AMEND. TO |
| | 2010 FBC SEC.107.2.1. |
| | 3) KNEE AND TOE CLEARANCES FOR THE LAVATORIES SHALL |
| | COMPLY WITH 2010 FAC SEC.306.SHOW THIS ON THE PLANS. |
| | 4) SHT. P1.1 - REFERENCE IS MADE TO THE 2007 FLORIDA |
| | BUILDING CODE. THE CODE IN EFFECT IS THE 2010 FBC. |
| | 5) SHTS.P1.1 & P3.1 - IDENTIFY THE EXISTING GREASE |
| | WASTE LINE AND THE FIXTURES THAT ARE DISCHARGING INTO |
| | IT. 2010 FPC SEC.1003.3.1. |
| | 6) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE |
| | EXISTING GREASE INTERCEPTOR AND THE SIZE OF THE GREASE |
| | INTERCEPTOR. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 7) SUBMIT SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR TO ENSURE THE CAPACITY IS ENOUGH FOR THIS |
| | APPLICATION.FPC SEC.1003.2 |
| | 8) SHT. P3.1 - SIZE THE WASTE STACK FOR THE URINAL.WPB |
| | AMEND. TO 2010 FBC SEC.107.2.1. |
| | 9)THE WATER CLOSET IN THE WOMEN'S RESTROOM IS BEING WET |
| | VENT WHICH PLACES THE URINAL ON A WET VENT WHICH IS NOT |
| | PERMITTED PER THE FPC SEC.909.1. |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED |
| | PER THE 2010 FGC SEC. 301.3. |
| | 11) SHT.P3.1 - THE TYPICAL GAS EQUIPMENT CONNECTION |
| | SHOWS A SYMBOL FOR A MEDIUM PRESSURE REGULATOR AND |
| | THERE APPEARS TO BE A MPR AT EACH APPLIANCE BUT THE |
| | NOTE STATES IT IS LESS THAN A 2 PSI SYSTEM. CLARIFY. |
| | 12)SHT. P3.1 - THE GAS LINE GOES FROM 1" TO 2". |
| | CLARIFY. |
| | 13) PROVIDE FOR THERMAL EXPANSION OF THE HOT WATER |
| | SYSTEM PER FPC SEC.607.3. |
| | 14) EQUIPMENT K-14 IS SHOWN ON THE FLOOR PLAN BUT NOT |
| | ON THE EQUIPMENT SCHEDULE OR RISER. CLARIFY. |
| | 15) THE BEVERAGE DISPENSERS SHALL BE EQUIPPED WITH |
| | BACKFLOW PREVENTERS TO PREVENT CARBON DIOXIDE FROM |
| | ENTERING THE WATER LINES. FPC SEC. 608.16.1. |
| | 16) COFFE MACINES AND NON-CARBONATED BEVERAGE |
| | DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW PER FPC |
| | SEC.608.16.10. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |