Plan Review Notes
Plan Review Notes For Permit 14110345
Permit Number 14110345
Review Stop P
Sequence Number 1
Notes
Date Text
2014-11-22 11:32:551)SUBMIT THE CORRECT OCCUPANT LOAD FOR THE SPACE. SHT.
 A2.0 SHOWS THREE DIFFERENT NUMBERS (248, 236, 172 ).
 THE MINIMUM SANITARY FACILITIES WILL BE BASED ON THE
 CORRECT OCCUPANT LOAD.
 2) SHT. A2.2 - ELEVS. #4 & # 8 - SUBMIT ELEVATIONS
 WHERE THE DIMENSIONS CAN BE CLEARLY READ. WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 3) KNEE AND TOE CLEARANCES FOR THE LAVATORIES SHALL
 COMPLY WITH 2010 FAC SEC.306.SHOW THIS ON THE PLANS.
 4) SHT. P1.1 - REFERENCE IS MADE TO THE 2007 FLORIDA
 BUILDING CODE. THE CODE IN EFFECT IS THE 2010 FBC.
 5) SHTS.P1.1 & P3.1 - IDENTIFY THE EXISTING GREASE
 WASTE LINE AND THE FIXTURES THAT ARE DISCHARGING INTO
 IT. 2010 FPC SEC.1003.3.1.
 6) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE
 EXISTING GREASE INTERCEPTOR AND THE SIZE OF THE GREASE
 INTERCEPTOR. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 7) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR TO ENSURE THE CAPACITY IS ENOUGH FOR THIS
 APPLICATION.FPC SEC.1003.2
 8) SHT. P3.1 - SIZE THE WASTE STACK FOR THE URINAL.WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 9)THE WATER CLOSET IN THE WOMEN'S RESTROOM IS BEING WET
 VENT WHICH PLACES THE URINAL ON A WET VENT WHICH IS NOT
 PERMITTED PER THE FPC SEC.909.1.
 10) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED
 PER THE 2010 FGC SEC. 301.3.
 11) SHT.P3.1 - THE TYPICAL GAS EQUIPMENT CONNECTION
 SHOWS A SYMBOL FOR A MEDIUM PRESSURE REGULATOR AND
 THERE APPEARS TO BE A MPR AT EACH APPLIANCE BUT THE
 NOTE STATES IT IS LESS THAN A 2 PSI SYSTEM. CLARIFY.
 12)SHT. P3.1 - THE GAS LINE GOES FROM 1" TO 2".
 CLARIFY.
 13) PROVIDE FOR THERMAL EXPANSION OF THE HOT WATER
 SYSTEM PER FPC SEC.607.3.
 14) EQUIPMENT K-14 IS SHOWN ON THE FLOOR PLAN BUT NOT
 ON THE EQUIPMENT SCHEDULE OR RISER. CLARIFY.
 15) THE BEVERAGE DISPENSERS SHALL BE EQUIPPED WITH
 BACKFLOW PREVENTERS TO PREVENT CARBON DIOXIDE FROM
 ENTERING THE WATER LINES. FPC SEC. 608.16.1.
 16) COFFE MACINES AND NON-CARBONATED BEVERAGE
 DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW PER FPC
 SEC.608.16.10.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  