2014-12-03 11:20:50THE OCCUPANCY #'S STATED DO NOT AGREE WITH THE
 VENTILATION SCHEDULE ON M1.1
 PLEASE CLARIFY THE NEED FOR ADDITIONAL A/C TONNAGE ON
 THE ENERGY CALC'S
 ANY ADDED SERVICABLE EQUIPTMENT ON THE ROOF WILL BE
 SUBJECT TO FBC 304.11 BELOW:
  
 304.11 GUARDS.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE AND ROOF
 HATCH OPENINGS ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND
 EACH END OF SUCH APPLIANCES, EQUIPMENT, FANS,
 COMPONENTS AND ROOF HATCH OPENINGS AND THE TOP OF THE
 GUARD SHALL BE LOCATED NOT LESS THAN 42 INCHES (1067
 MM) ABOVE THE ELEVATED SURFACE ADJACENT TO THE GUARD.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE AND SHALL
 COMPLY WITH THE LOADING REQUIREMENTS FOR GUARDS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW THE SHAFT WALL CLEARANCES ON A2.3 DETAIL 4 WITH
 REGARD TO FBC-M 506.3.10 THRU 506.3.10.2 BELOW:
  
 506.3.10 GREASE DUCT ENCLOSURES.
 A GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A
 FIRE-RATED CEILING, FIRE-RATED WALL OR FLOOR SHALL BE
 ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET
 TERMINAL. A DUCT SHALL PENETRATE EXTERIOR WALLS ONLY AT
 LOCATIONS WHERE UNPROTECTED OPENINGS ARE PERMITTED BY
 THE FLORIDA BUILDING CODE, BUILDING. THE DUCT ENCLOSURE
 SHALL SERVE A SINGLE GREASE DUCT AND SHALL NOT CONTAIN
 OTHER DUCTS, PIPING OR WIRING SYSTEMS. DUCT ENCLOSURES
 SHALL BE EITHER FIELD-APPLIED OR FACTORY-BUILT. DUCT
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS
 THAN THAT OF THE FLOOR ASSEMBLY PENETRATED, BUT NEED
 NOT EXCEED 2 HOURS. DUCT ENCLOSURES SHALL BE AS
 PRESCRIBED BY SECTION 506.3.10.1, 506.3.10.2 OR
 506.3.10.3. THE ENCLOSURE SHALL BE SEPARATED FROM THE
 DUCT BY A MINIMUM OF 6 INCHES (152 MM) AND A MAXIMUM OF
 12 INCHES (305MM) AND SHALL SERVE A SINGLE GREASE
 EXHAUST DUCT SYSTEM.
  
 506.3.10.1 SHAFT ENCLOSURE.
 COMMERCIAL KITCHEN GREASE DUCTS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 506.3.1 SHALL BE PERMITTED TO
 BE ENCLOSED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING REQUIREMENTS FOR SHAFT CONSTRUCTION.
 SUCH GREASE DUCT SYSTEMS AND EXHAUST EQUIPMENT SHALL
 HAVE A CLEARANCE TO COMBUSTIBLE CONSTRUCTION OF NOT
 LESS THAN 18 INCHES (457 MM), AND SHALL HAVE A
 CLEARANCE TO NONCOMBUSTIBLE CONSTRUCTION AND GYPSUM
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES OF NOT
 LESS THAN 6 INCHES (76 MM). DUCT ENCLOSURES SHALL BE
 SEALED AROUND THE DUCT AT THE POINT OF PENETRATION AND
 VENTED TO THE OUTSIDE OF THE BUILDING THROUGH THE USE
 OF WEATHER-PROTECTED OPENINGS.
  
 506.3.10.2 FIELD-APPLIED GREASE DUCT ENCLOSURE.
 COMMERCIAL KITCHEN GREASE DUCTS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 506.3.1 SHALL BE ENCLOSED BY A
 FIELD-APPLIED GREASE DUCT ENCLOSURE THAT IS A LISTED
 AND LABELED MATERIAL, SYSTEM, PRODUCT OR METHOD OF
 CONSTRUCTION SPECIFICALLY EVALUATED FOR SUCH PURPOSE IN
 ACCORDANCE WITH ASTM E 2336. THE SURFACE OF THE DUCT
 SHALL BE CONTINUOUSLY COVERED ON ALL SIDES FROM THE
 POINT AT WHICH THE DUCT ORIGINATES TO THE OUTLET
 TERMINAL. DUCT PENETRATIONS SHALL BE PROTECTED WITH A
 THROUGH-PENETRATION FIRESTOP SYSTEM CLASSIFIED AND
 INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E 814 OR UL
 1479 AND HAVING AN ?F? AND ?T? RATING OF NOT LESS THAN
 1 HOUR, BUT NOT LESS THAN THE FIRE-RESISTANCE RATING OF
 THE ASSEMBLY BEING PENETRATED. SUCH SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE LISTING AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. EXPOSED DUCT
 WRAP SYSTEMS SHALL BE PROTECTED WHERE SUBJECT TO
 PHYSICAL DAMAGE.