Plan Review Notes
Plan Review Notes For Permit 14110345
Permit Number 14110345
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-19 07:58:0912/19/2014
 PROJECT: B&B
 PERMIT#: 14110345
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) VERIFY MAIN SERVICE ENTRANCE CONDUCTORS ARE APPROVED
 TO SUPPORT TOTAL CONNECTED LOAD. THERE IS NO SIZE
 INDICATED ON THE RISER DIAGRAM.
  
 2) CORRECT NOTE 5 ON PANEL SCHEDULE "B" THAT CALLS FOR
 A 150AMP CIRCUIT BREAKER TO FEED PANEL "A". THERE IS A
 CONFLICTING NOTE ON THE RISER DIAGRAM THAT CALLS FOR
 THAT TO BE A 200AMP BREAKER. PLEASE CLARIFY.
  
 3) VERIFY EXISTING WIREWAY IS ADAQUATE SIZE FOR THE NEW
 SERVICE.
  
 4) PROVIDE GFCI PROTECTION WHERE RECEPTACLES OUTLETS
 ARE INSTALLED WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE
 OF A SINK.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  