| Plan Review Notes For Permit 14110345 |
| Permit Number |
14110345 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-19 07:58:09 | 12/19/2014 | | | PROJECT: B&B | | | PERMIT#: 14110345 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION | | | | | | 1) VERIFY MAIN SERVICE ENTRANCE CONDUCTORS ARE APPROVED | | | TO SUPPORT TOTAL CONNECTED LOAD. THERE IS NO SIZE | | | INDICATED ON THE RISER DIAGRAM. | | | | | | 2) CORRECT NOTE 5 ON PANEL SCHEDULE "B" THAT CALLS FOR | | | A 150AMP CIRCUIT BREAKER TO FEED PANEL "A". THERE IS A | | | CONFLICTING NOTE ON THE RISER DIAGRAM THAT CALLS FOR | | | THAT TO BE A 200AMP BREAKER. PLEASE CLARIFY. | | | | | | 3) VERIFY EXISTING WIREWAY IS ADAQUATE SIZE FOR THE NEW | | | SERVICE. | | | | | | 4) PROVIDE GFCI PROTECTION WHERE RECEPTACLES OUTLETS | | | ARE INSTALLED WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE | | | OF A SINK. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | | | | | |
|