| Plan Review Notes For Permit 14110342 |
| Permit Number |
14110342 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-11-14 16:42:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE SHUTTER INSTALLATION SCHEDULE SUBMITTED HAS | | | "CONC BLOCK" FOR SUBSTRATE AND ELCO PANEL MATE FOR | | | FASTENER. SEE ANCHOR CHART ON SHEET 4. HORIZONTAL | | | INSTALLATIONS HAVE A BLOCK SUBSTRATE (FILLED CELLS ARE | | | BLOCK, NOT CONCRETE). VERTICAL INSTALLATIONS USUALLY | | | HAVE CONCRETE TOP, BLOCK BOTTOM. THE FASTENER SELECTED | | | CANNOT BE USED WITH A BLOCK SUBSTRATE. | | | | | | FBC 2010 RESIDENTIAL 301. | | | |
|