Plan Review Notes
Plan Review Notes For Permit 14110342
Permit Number 14110342
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-08 11:37:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A FLOOR PLAN WHICH SHOWS PROPOSED LOCATIONS
 OF PROPOSED NEW SHUTTERS, FBC 107. A PLAN WAS PROVIDED
 BUT THE OPENINGS ARE NOT NUMBERED TO CORRELATE WITH THE
 INSTALLATION SCHEDULE.
  
 2. THE SHUTTER INSTALLATION SCHEDULE IS INCOMPLETE.
 PROVIDE SPAN AND SHUTTER GLASS SEPARATION AND SELECT
 ONE SHUTTER CONNECTION MOUNTING TYPE. I HAD PROVIDED
 THE INFORMATION WHICH CONTRACTORS FIND MOST DIFFICULT
 TO COMPLETE. CONTRACTOR IS TO PROVIDE THE REMAINING
 INFORMATION WITH THE EXCEPTION OF WALL PRESSURES
 (COLUMN 3) AND THE LAST COLUMN. THE EXAMPLE I GAVE WAS
 AN EXAMPLE. I PROVIDED WORST CASE FOR C1 AND C2. PLEASE
 PROVIDE AN INSTALLATION SCHEDULE WHICH SPECIFIES WHICH
 ONE OF THE TWO METHODS WILL BE INSTALLED; FBC 107, FBC
 2010 RESIDENTIAL 301.
  
 3. IMPACT DOOR PRODUCT APPROVALS WERE PROVIDED. FOR
 THIS SHUTTER PERMIT, ONLY SHUTTER INFORMATION IS
 REQUIRED. THE DOOR PRODUCT APPROVALS SHOULD BE INCLUDED
 EITHER IN THE ORIGINAL PERMIT APPLICATION OR THE
 PENDING REVISION #14110277.
  
  
  