| 2015-01-26 13:40:53 | 01/07/2015 |
| | PROJECT: PARMALEE RESIDENCE |
| | PERMIT#: 14110286 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. |
| | |
| | PROVIDE REVISED ELECTRICAL PLANS ADDRESSING THE |
| | FOLLOWING COMMENTS PRIOR TO INSPECTION. |
| | |
| | 1) FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN |
| | FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE. FBC WPB AMENDMENTS. SECTION 109.3. |
| | REVISE THE VALUE ON THE APPLICATION OR PROVIDE |
| | SUPPORTING DOCUMENTATION OF THE ACTUAL COST OF THE |
| | ELECTRICAL INSTALLATION INCLUDING ALL OF THE ABOVE |
| | REFERENCED CRITERIA. |
| | |
| | 2) PROVIDE A REVISED RISER DIAGRAM INDICATING THE |
| | CORRECT WIRE SIZE IN ALL CONDUITS. EXISTING SERVICE |
| | ENTRANCE TO BE ADEQUATE FOR THE 250A MAIN OCPD. FOR THE |
| | 250A. SERVICE ENTRANCE AND FEEDER A MINIMUM 4/0CU IS |
| | REQUIRED. NEC T-310.15(B)(6). |
| | |
| | 3) PROVIDE A REVISED PANEL SCHEDULE FOR PANEL "A" AND A |
| | NEW PANEL SCHEDULE FOR PANEL "B". EVERY CIRCUIT AND |
| | CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO |
| | ITS CLEAR, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | INCLUDE ALL NEW CIRCUITS FOR LANDSCAPE LIGHTING, |
| | FOUNTAIN PUMPS, AND HARDSCAPE FEATURES. |
| | |
| | 4) REVISE LOAD CALCULATION AS DESCRIBED IN THE NEC |
| | 220.12 , 220.14. LOADS FOR NEW CIRCUITS OR EXTENDED |
| | CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE |
| | CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14, |
| | AS APPLICABLE. NEC 220.16(2) |
| | |
| | 5) PROVIDE LOCATIONS AND ELEVATIONS FOR ALL ELECTRICAL |
| | EQUIPMENT, TRANSFORMERS AND JUNCTION BOXES IN |
| | COMPLIANCE WITH NEC 682. |
| | |
| | 6) ALL PERMANENTLY INSTALLED FOUNTAINS SHALL COMPLY |
| | WITH NEC 680.50 AS DEFINED IN 680.2. |
| | |
| | 7) INDICATE THE VOLTAGE ON EACH OF THE FIXTURES. |
| | INDICATE THE TYPE AND SIZE OF CABLE FOR EACH CIRCUIT. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |