Plan Review Notes
Plan Review Notes For Permit 14110284
Permit Number 14110284
Review Stop E
Sequence Number 3
Notes
Date Text
2015-01-26 13:40:5301/07/2015
 PROJECT: PARMALEE RESIDENCE
 PERMIT#: 14110286
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION.
  
 PROVIDE REVISED ELECTRICAL PLANS ADDRESSING THE
 FOLLOWING COMMENTS PRIOR TO INSPECTION.
  
 1) FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. FBC WPB AMENDMENTS. SECTION 109.3.
 REVISE THE VALUE ON THE APPLICATION OR PROVIDE
 SUPPORTING DOCUMENTATION OF THE ACTUAL COST OF THE
 ELECTRICAL INSTALLATION INCLUDING ALL OF THE ABOVE
 REFERENCED CRITERIA.
  
 2) PROVIDE A REVISED RISER DIAGRAM INDICATING THE
 CORRECT WIRE SIZE IN ALL CONDUITS. EXISTING SERVICE
 ENTRANCE TO BE ADEQUATE FOR THE 250A MAIN OCPD. FOR THE
 250A. SERVICE ENTRANCE AND FEEDER A MINIMUM 4/0CU IS
 REQUIRED. NEC T-310.15(B)(6).
  
 3) PROVIDE A REVISED PANEL SCHEDULE FOR PANEL "A" AND A
 NEW PANEL SCHEDULE FOR PANEL "B". EVERY CIRCUIT AND
 CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO
 ITS CLEAR, AND SPECIFIC PURPOSE OR USE. NEC 408.4
 INCLUDE ALL NEW CIRCUITS FOR LANDSCAPE LIGHTING,
 FOUNTAIN PUMPS, AND HARDSCAPE FEATURES.
  
 4) REVISE LOAD CALCULATION AS DESCRIBED IN THE NEC
 220.12 , 220.14. LOADS FOR NEW CIRCUITS OR EXTENDED
 CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14,
 AS APPLICABLE. NEC 220.16(2)
  
 5) PROVIDE LOCATIONS AND ELEVATIONS FOR ALL ELECTRICAL
 EQUIPMENT, TRANSFORMERS AND JUNCTION BOXES IN
 COMPLIANCE WITH NEC 682.
  
 6) ALL PERMANENTLY INSTALLED FOUNTAINS SHALL COMPLY
 WITH NEC 680.50 AS DEFINED IN 680.2.
  
 7) INDICATE THE VOLTAGE ON EACH OF THE FIXTURES.
 INDICATE THE TYPE AND SIZE OF CABLE FOR EACH CIRCUIT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  