Plan Review Notes
Plan Review Notes For Permit 14110284
Permit Number 14110284
Review Stop E
Sequence Number 2
Notes
Date Text
2015-01-07 10:59:5501/07/2015
 PROJECT: PARMALEE RESIDENCE
 PERMIT#: 14110286
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE
 REQUIRED FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT.
 ONCE REVIEWED AND READY FOR ISSUANCE, ONE SET TO BE
 RETAINED BY THE BUILDING OFFICIAL FOR THE PURPOSE OF
 RECORD KEEPING AND THE OTHER TO BE RETURNED TO THE
 APPLICANT UPON ISSUANCE OF THE PERMIT. WPB AMENDMENTS
 TO THE FBC 107.3.1 SUBMITTAL DOCUMENTS.
 WHILE THERE ARE TWO SETS OF ELECTRICAL PLANS ( E-1 AND
 E-2 SHEETS) THE BALANCE OF THE SUBMITTAL IS A MIX. IN
 ONE SET THERE IS ONE SET OF HARDSCAPE PLANS AND DETAILS
 (H-1 THROUGH H-5) AND FIRST SET OF ELECTRICAL PLANS
 (E-1 AND E-2), HOWEVER THE OTHER SET INCLUDES ONE SET
 OF LANDSCAPE LIGHTING PLANS(LLP-1, LLP-2, AND LLP-3,
 ONE SET OF PLUMBING PLANS (P.1 AND P.2) AND THE SECOND
 SET OF ELECTRICAL (E-1 AND E-2 SHEETS) PROVIDE TWO
 COMPLETE SETS OF CONSTRUCTION DOCUMENTS FOR REVIEW.
  
 2) FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. FBC WPB AMENDMENTS. SECTION 109.3.
 REVISE THE VALUE ON THE APPLICATION OR PROVIDE
 SUPPORTING DOCUMENTATION OF THE ACTUAL COST OF THE
 ELECTRICAL INSTALLATION INCLUDING ALL OF THE ABOVE
 REFERENCED CRITERIA.
  
 3) PROVIDE A REVISED PANEL SCHEDULE FOR PANEL "A" AND A
 NEW PANEL SCHEDULE FOR PANEL "B". EVERY CIRCUIT AND
 CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO
 ITS CLEAR, AND SPECIFIC PURPOSE OR USE. NEC 408.4
 INCLUDE ALL NEW CIRCUITS FOR LANDSCAPE LIGHTING,
 FOUNTAIN PUMPS, AND HARDSCAPE FEATUES.
  
 4) PROVIDE THE LOCATIONS FOR THE ELECTRICAL SERVICE,
 ELECTRICAL PANELS "A" AND "B" AND ALL NEW CIRCUITRY ON
 THE SITE (LLP'S) PLANS INCLUDING ALL NEW CIRCUITS FOR
 LANDSCAPE LIGHTING, FOUNTAIN PUMPS, AND HARDSCAPE
 FEATUES. IDENTIFY THE VOLTAGE AND THE CIRCUIT NUMBERS
 CORRESPONDING TO THE PANEL SCHEDULE(S)
  
 5) REVISE LOAD CALCULATION AS DESCRIBED IN THE NEC
 220.12 , 220.14. LOADS FOR NEW CIRCUITS OR EXTENDED
 CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14,
 AS APPLICABLE. NEC 220.16(2)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  