| 2015-01-07 10:59:55 | 01/07/2015 |
| | PROJECT: PARMALEE RESIDENCE |
| | PERMIT#: 14110286 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE |
| | REQUIRED FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT. |
| | ONCE REVIEWED AND READY FOR ISSUANCE, ONE SET TO BE |
| | RETAINED BY THE BUILDING OFFICIAL FOR THE PURPOSE OF |
| | RECORD KEEPING AND THE OTHER TO BE RETURNED TO THE |
| | APPLICANT UPON ISSUANCE OF THE PERMIT. WPB AMENDMENTS |
| | TO THE FBC 107.3.1 SUBMITTAL DOCUMENTS. |
| | WHILE THERE ARE TWO SETS OF ELECTRICAL PLANS ( E-1 AND |
| | E-2 SHEETS) THE BALANCE OF THE SUBMITTAL IS A MIX. IN |
| | ONE SET THERE IS ONE SET OF HARDSCAPE PLANS AND DETAILS |
| | (H-1 THROUGH H-5) AND FIRST SET OF ELECTRICAL PLANS |
| | (E-1 AND E-2), HOWEVER THE OTHER SET INCLUDES ONE SET |
| | OF LANDSCAPE LIGHTING PLANS(LLP-1, LLP-2, AND LLP-3, |
| | ONE SET OF PLUMBING PLANS (P.1 AND P.2) AND THE SECOND |
| | SET OF ELECTRICAL (E-1 AND E-2 SHEETS) PROVIDE TWO |
| | COMPLETE SETS OF CONSTRUCTION DOCUMENTS FOR REVIEW. |
| | |
| | 2) FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN |
| | FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE. FBC WPB AMENDMENTS. SECTION 109.3. |
| | REVISE THE VALUE ON THE APPLICATION OR PROVIDE |
| | SUPPORTING DOCUMENTATION OF THE ACTUAL COST OF THE |
| | ELECTRICAL INSTALLATION INCLUDING ALL OF THE ABOVE |
| | REFERENCED CRITERIA. |
| | |
| | 3) PROVIDE A REVISED PANEL SCHEDULE FOR PANEL "A" AND A |
| | NEW PANEL SCHEDULE FOR PANEL "B". EVERY CIRCUIT AND |
| | CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO |
| | ITS CLEAR, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | INCLUDE ALL NEW CIRCUITS FOR LANDSCAPE LIGHTING, |
| | FOUNTAIN PUMPS, AND HARDSCAPE FEATUES. |
| | |
| | 4) PROVIDE THE LOCATIONS FOR THE ELECTRICAL SERVICE, |
| | ELECTRICAL PANELS "A" AND "B" AND ALL NEW CIRCUITRY ON |
| | THE SITE (LLP'S) PLANS INCLUDING ALL NEW CIRCUITS FOR |
| | LANDSCAPE LIGHTING, FOUNTAIN PUMPS, AND HARDSCAPE |
| | FEATUES. IDENTIFY THE VOLTAGE AND THE CIRCUIT NUMBERS |
| | CORRESPONDING TO THE PANEL SCHEDULE(S) |
| | |
| | 5) REVISE LOAD CALCULATION AS DESCRIBED IN THE NEC |
| | 220.12 , 220.14. LOADS FOR NEW CIRCUITS OR EXTENDED |
| | CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE |
| | CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14, |
| | AS APPLICABLE. NEC 220.16(2) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |