 PROJECT: PARMALEE RESIDENCE
 PERMIT#: 14110286
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE
 REQUIRED FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT.
 ONCE REVIEWED AND READY FOR ISSUANCE, ONE SET TO BE
 RETAINED BY THE BUILDING OFFICIAL FOR THE PURPOSE OF
 RECORD KEEPING AND THE OTHER TO BE RETURNED TO THE
 APPLICANT UPON ISSUANCE OF THE PERMIT. WPB AMENDMENTS
 TO THE FBC 107.3.1 SUBMITTAL DOCUMENTS.
  
 2) FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. FBC WPB AMENDMENTS. SECTION 109.3.
 REVISE THE VALUE ON THE APPLICATION OR PROVIDE
 SUPPORTING DOCUMENTATION OF THE ACTUAL COST OF THE
 ELECTRICAL INSTALLATION INCLUDING ALL OF THE ABOVE
 REFERENCED CRITERIA.
  
 3) REVISE THE RISER DIAGRAM TO INDICATE AN APPROVED
 CONDUCTOR SIZE ADEQUATE TO SUPPORT THE 250AMP MAIN IN
 PANEL A. THE 3/0 CONDUCTORS IN THE RISER ARE
 UNDERSIZED. NEC 310.15(B(6) OR 310.16
  
 4) PROVIDE A REVISED PANEL SCHEDULE FOR PANEL A. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 5) PROVIDE A PANEL SCHEDULE FOR NEW PANEL B. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 6) INDICATE THE LOCATIONS OF THE NEW CIRCUITRY ON THE
 PLANS. IDENTIFY THE VOLTAGE OF EACH CIRCUIT, THE
 CIRCUIT NUMBERS CORRESPONDING TO THE PANEL SCHEDULE AND
 THE LOCATION OF THE REMOTE TRANSFORMERS.
  
 7) REVISE LOAD CALCULATION AS DESCRIBED IN THE NEC
 220.12 , 220.14. LOADS FOR NEW CIRCUITS OR EXTENDED
 CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14,
 AS APPLICABLE. NEC 220.16(2)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  