| 2014-11-10 11:33:30 | PERMIT #14110235 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REVIEW FAILED: | | | 1) 2 COPIES OF ALL SUBMITTED PLANS SHEETS AND DATA | | | SHEETS MUST BE SUBMITTED. ONLY 1 COPY PROVIDED. | | | 2) PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL | | | BE LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10 | | | FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST | | | SYSTEM. THIS IS NOT OUTLINED IN NARRATIVE, NOR IS IT | | | INDICATED ON THE LAYOUT SHEET SUBMITTED. | | | 3) LAYOUT SHEET PROVIDED IS NOT CLEAR ON ACTUAL | | | APPLIANCES USED AND THEIR LOCATIONS/LAYOUT IN REFERENCE | | | TO KITCHEN SETUP. A BETTER LAYOUT SHEET NEEDS TO BE | | | PROVIDED, THAT SHOWS THE APPLIANCES, THEIR LAYOUT, AND | | | THE KITCHEN LAYOUT. PLAN SHOULD INDICATE LOCATION OF | | | MANUAL ACTIVATION DEVICE, CLASS K EXTINGUISHER, ETC. | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|