2014-11-10 11:33:30PERMIT #14110235
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVIEW FAILED:
 1) 2 COPIES OF ALL SUBMITTED PLANS SHEETS AND DATA
 SHEETS MUST BE SUBMITTED. ONLY 1 COPY PROVIDED.
 2) PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL
 BE LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THIS IS NOT OUTLINED IN NARRATIVE, NOR IS IT
 INDICATED ON THE LAYOUT SHEET SUBMITTED.
 3) LAYOUT SHEET PROVIDED IS NOT CLEAR ON ACTUAL
 APPLIANCES USED AND THEIR LOCATIONS/LAYOUT IN REFERENCE
 TO KITCHEN SETUP. A BETTER LAYOUT SHEET NEEDS TO BE
 PROVIDED, THAT SHOWS THE APPLIANCES, THEIR LAYOUT, AND
 THE KITCHEN LAYOUT. PLAN SHOULD INDICATE LOCATION OF
 MANUAL ACTIVATION DEVICE, CLASS K EXTINGUISHER, ETC.
  