Plan Review Notes
Plan Review Notes For Permit 14110234
Permit Number 14110234
Review Stop M
Sequence Number 3
Notes
Date Text
2015-07-09 07:36:383RD REVIEW: FBC 2010 MECHANICAL
 7/9/2015
  
 1) PROVIDE A MEANS OF VENTILATION FOR THE NEW STORAGE
 ROOM- TABLE 403.3 FBC-10 MECHANICAL.
 2) THE NEW HVAC PLAN INDICATES 8"X8" CEILING REGISTERS
 IN THE CATERING KITCHEN, HOWEVER THE PARTIAL MEP PLAN
 ON SHEET 2 INDICATES 2'X2' DIFFUSERS: PLEASE CORRECT.
  