| Plan Review Notes For Permit 14110213 |
| Permit Number |
14110213 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-01-17 06:29:46 | 1) A MINIMUM OF THREE DRINKING FOUNTAINS ARE REQUIRED | | | PER TABLE 403. THE RESPONSE REFERS TO REFRIGERATORS IN | | | THE COFFEE BREAK ROOM #453 & EMPLOYEE BREAK ROOM #412 | | | HAVING WATER DISPENSERS. SHOW HOW THESE WATER | | | DISPENSERS COMPLY WITH ARI 1010 AND NSF 61. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|