2015-01-14 11:07:42BUILDING PLAN REVIEW
 PERMIT: 14110213
 ADD: 222 LAKEVIEW SUITE # 400
 CONT: GREEN CONSTRUCTION
 TEL: (305) 670-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN 14/2015
 ACTION: DENIED
  
 NOTICE: THE PERMIT APPLICATION INDICATES UNDER THE
 HEADING DESCRIPTION OF WORK, TYPED SUITE 400/
 HANDWRITTEN 1ST FLOOR BUILD OUT. THE PLANS INDICATE THE
 WORK IS TO BE COMPLETED ON THE 4TH FLOOR, SO THIS
 REVIEW WILL TAKE PLACE AS 4TH FLOOR. CORRECT THE PERMIT
 APPLICATION.
  
 1) SHEET A-04:
 !A) THE (2) NEW ELEVATORS THAT ARE NOT PART OF THIS
 CONTRACT WILL EFFECT THE OUTCOME OF THIS PROJECT,
 PLEASE INDICATE HOW COMPLIANCE WITH FBC-B 708.14.1
 ELEVATOR LOBBIES OR A EXCEPTION WILL BE COMPLIED WITH.
 THE RESPONSE INDICATES TO SEE ENGINEERING PLANS AND
 PLEASE NOTE THE PROPOSED ELEVATOR WILL NOT BE SERVING
 MORE THAN 3 FLOORS.
  
 IN THE MECHANICAL PLANS SHEET M1.2 THERE IS NO MENTION
 OF SHAFT PRESSURIZATION OR ANY EXCEPTION.PLEASE REVIEW
 THE FOLLOWING INFORMAL INTERPRETATION REPORT 7397.
  
 DATE: WED SEP 10 2014
 REPORT: 7397
 CODE: BUILDING CODE YEAR: 2010
 SECTION: 708.14.1
 QUESTION:
 IS IT THE INTENT OF THIS SECTION TO REQUIRE ELEVATOR
 LOBBIES OR THEIR EXCEPTION IN NEW ELEVATORS AND
 SHAFTWAYS IN A PORTION OF A
 HIGHRISE BUILDING THAT IS (5) STORIES IN HEIGHT IF YES
 THEN WOULD THE EXCEPTIONS APPLY?
 COMMENT:
 NONE
 ANSWER:
 YES AND YES
 COMMENTARY:
 A HIGH RISE BUILDING IS DEFINED BY ITS HEIGHT (OCCUPIED
 FLOOR GREATER THAN 75? ABOVE LOWEST LEVEL OF FIRE DEPT.
 VEHICULAR ACCESS);
 NOT THE NUMBER OF FLOORS. AS A NOTE, THE NEXT EDITION
 OF THE CODE WILL ALLOW THE DELETION OF LOBBIES FOR AN
 ELEVATOR IN A HIGH RISE
 BUILDING THAT DOES NOT SERVE FLOORS OVER 75 FEET ABOVE
 THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS.
 I.E. THE LOWER FLOORS OF
 A HIGH RISE BUILDING SERVED BY AN ELEVATOR SERVING ONLY
 THE LOWER FLOORS. (THE FIRST 5 STORIES, IF THEY DO NOT
 HAVE AN OCCUPIED
 FLOOR LEVEL MORE THAN 75 FEET ABOVE FD VEHICLE ACCESS
 AND THE ELEVATOR DOES NOT SERVICE ANY SUCH FLOOR. THE
 PROVISION WILL MOVE
 TO SECTION 713.14.1 IN THE NEXT EDITION. HERE IS THE
 WORDING THAT WILL BE COMING IN THE NEXT EDITION: 4.
 ENCLOSED ELEVATOR LOBBIES
 ARE NOT REQUIRED WHERE THE BUILDING IS PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH
 SECTION
 903.3.1.1 OR 903.3.1.2. THIS EXCEPTION SHALL NOT APPLY
 TO THE FOLLOWING: 4.1. GROUP I-2 OCCUPANCIES; 4.2.
 GROUP I-3 OCCUPANCIES;
 AND 4.3. ELEVATORS SERVING FLOOR LEVELS OVER 75 FEET
 (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS IN
 HIGH-RISE BUILDINGS
 NOTICE:
 THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN
 COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC,
 AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS
 INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE
 INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE.
 THIS INTERPRETATION IS INFORMAL, NON-BINDING AND
 SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL
 BUILDING OFFICIAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER