2014-12-02 11:53:5612/2/2014
 PROJECT: DADELAND CENTER.STE 400
 PERMIT#: 14110213
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION:DENIED
  
 1) PROVIDE MANUFACTURER PRODUCT SPEC SHEETS FOR AUTO
 FLUSH AND LAV VALVES INDICATING THE OPERATING VOLTAGE
 AND COMPLIANCE WITH THE LISTING REQUIREMENTS OF THE NEC
 110.3(B)
  
 2) INDICATE LOCATION, SIZE, TYPE, PHASE AND VOLTAGE FOR
 SERVICE DISCONNECT SD-1 AND SD-2. FBC- 107.3.5.3
  
 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SECURITY, CCTV, NETWORK, DATA,
 COMMUNICATION, FIRE ALARM, ACCESS CONTROL SYSTEM,
 AUDIO, VIDEO.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  