Plan Review Notes
Plan Review Notes For Permit 14110213
Permit Number 14110213
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-17 14:21:00BUILDING PLAN REVIEW
 PERMIT: 14110213
 ADD: 222 LAKEVIEW SUITE # 400
 CONT: GREEN CONSTRUCTION
 TEL: (305) 670-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 17/2014
 ACTION: DENIED
  
 NOTICE: THE PERMIT APPLICATION INDICATES UNDER THE
 HEADING DESCRIPTION OF WORK, TYPED SUITE 400/
 HANDWRITTEN 1ST FLOOR BUILD OUT. THE PLANS INDICATTE
 THE WORK IS TO BE COMPLETED ON THE 4TH FLOOR, SO THIS
 REVIEW WILL TAKE PLACE AS 4TH FLOOR. CORRECT THE PERMIT
 APPLICATION.
  
 1) 1) SHEET A-04:
 !A) THE (2) NEW ELEVATORS THAT ARE NOT PART OF THIS
 CONTRACT WILL EFFECT THE OUTCOME OF THIS PROJECT,
 PLEASE INDICATE HOW COMPLIANCE WITH FBC-B 708.14.1
 ELEVATOR LOBBIES OR A EXCEPTION WILL BE COMPLIED WITH.
  
  
 1B) THE (2) STORAGE ROOMS 403 & 436 ARE LARGE FILE
 ROOMS PLEASE PROVIDE WHAT THE FLOOR LOADS FOR THESE
 ROOMS ARE DESIGNED, SEE 2010 FBC-B TABLE
 1607.1 (25) OFFICE BUILDINGS- FILE ROOMS SHALL BE
 DESIGNED FOR HEAVIER LOADS BASED ON ANTICIPATED
 OCCUPANCY.
  
 1C) THE COFFEE/ BREAK ROOM # 456 INDICATES A SECTION/
 DETAIL 3/ A-09 THIS IS NOT THE CORRECT DETAILS. SHEET
 A-07.6 SHOWS VARIOUS SINK DETAILS.
 PLEASE PROVIDE CORRECT SECTION. 107.2.1.3 DISCREPANCY
 IN PLANS.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  