| Notes |
| Date |
Text |
| 2014-11-15 12:29:31 | ***PROVISO**** | | | 1) THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL | | | BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE | | | SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR | | | FROM THE REAR WALL. FAC SEC.604.3.1. | | | 2) THE REQUIRED 30 INCH X 48 INCH CLEAR FLOOR SPACE | | | REQUIRED FOR THE DRINKING FOUNTAIN SHALL BE CENTERED ON | | | THE INDIVIDUAL UNIT AND NOT ON BOTH UNITS. FAC 602.2. | | | 3) KNEE & TOE CLEARANCE FOR DRINKING FOUNTAIN SHALL | | | COMPLY W/ FAC SEC. 305 | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|