| 2014-11-15 13:18:03 | PROVISIONAL APPROVAL BASED ON THE FIRE PLANS EXAMINER'S | | | NOTES. | | | | | | 1) ALL INITIATION DEVICES TO BE INSTALLAED AS | | | ADDRESSSABLE DEVICES. | | | 2) TWO STROBES ARE BEING UPGRADED TO SPEAKER STROBES. | | | PROVIDE CUT SHEETS TO ENSURE THE EXISTING GAUGE OF WIRE | | | IS ADAQUATE AND COMPATIBLE WITH MANUFACTURER'S | | | RECOMENDATIONS. | | | 3) PROVIDE A BATTERY CALCULATION TO ENSURE THE EXISTING | | | CAPACITY IS ADAQUATE FOR THE ADDITIONAL LOAD. | | | 4) REMOVAL OF ANY DEVICE TO SHOW TROUBLE AT THE FACP. | | | 5) SUBMIT REVISED PLANS TO INDICATE CURRENT AND ACTUAL | | | LOCATION OF PULL STATIONS. AND TO FU8LFILL ALL | | | REQUIREMENTS ABOVE. |
|