| 2014-11-06 08:36:18 | RESIDENTIAL (R3) WINDOW REPLACEMENT, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE 2 COPIES OF THE WINDOW AND MULLIONS NOA'S. |
| | ONLY ONE COPY OF EACH WAS SUBMITTED. REQUIRED BY SEC. |
| | 107.1 CITY AMENDMENTS TO FBC. |
| | |
| | 2- CLARIFY TOTAL NUMBER OF WINDOWS TO BE REPLACED. |
| | PERMIT APPLICATION AND FLOOR PLAN SKETCH SUBMITTED SAYS |
| | REPLACING 18 WINDOWS. BUT, COPY OF OF WINDOW ORDER |
| | SUBMITTED SAYS 12 32"X58" WINDOWS. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 3- CLEARLY SPECIFY SIZE OF ALL BEDROOM WINDOWS, |
| | INCLUDING SECOND FLOOR WINDOWS IF THERE IS ANY BEDROOM |
| | UP THERE. ARE THEY 32" X 58" AS SPECIFIED ON THE WINDOW |
| | ORDER?. NEED THIS INFORMATION TO VERIFY COMPLIANCE WITH |
| | THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010 |
| | FBC-EXISTING BUILDING. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| | CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| | 109.3 CITY AMENDMENTS TO FBC. VALUE IS DETERMINED EVEN |
| | IF THE OWNER IS DOING THE LABOR. VALUATION WAS UPDATED |
| | TO $3,600. THIS VALUE IS FOR REPLACEMENT OF 18 WINDOWS. |
| | |
| | 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713 OF FLORIDA STATUES. |
| | |