2014-11-06 08:36:18RESIDENTIAL (R3) WINDOW REPLACEMENT, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE 2 COPIES OF THE WINDOW AND MULLIONS NOA'S.
 ONLY ONE COPY OF EACH WAS SUBMITTED. REQUIRED BY SEC.
 107.1 CITY AMENDMENTS TO FBC.
  
 2- CLARIFY TOTAL NUMBER OF WINDOWS TO BE REPLACED.
 PERMIT APPLICATION AND FLOOR PLAN SKETCH SUBMITTED SAYS
 REPLACING 18 WINDOWS. BUT, COPY OF OF WINDOW ORDER
 SUBMITTED SAYS 12 32"X58" WINDOWS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 3- CLEARLY SPECIFY SIZE OF ALL BEDROOM WINDOWS,
 INCLUDING SECOND FLOOR WINDOWS IF THERE IS ANY BEDROOM
 UP THERE. ARE THEY 32" X 58" AS SPECIFIED ON THE WINDOW
 ORDER?. NEED THIS INFORMATION TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010
 FBC-EXISTING BUILDING.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS TO FBC. VALUE IS DETERMINED EVEN
 IF THE OWNER IS DOING THE LABOR. VALUATION WAS UPDATED
 TO $3,600. THIS VALUE IS FOR REPLACEMENT OF 18 WINDOWS.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713 OF FLORIDA STATUES.
  