| 2014-11-17 05:16:22 | 1) SHT.A-1 - H.C. LAVATORY DETAIL - THE PLAN VIEW OF |
| | THE TOILET ROOM SHOWS A 48" X 56 " CLEARANCE FOR THE |
| | WATER CLOSET. SEC. 603.3.1. OF THE 2010 FL. |
| | ACCESSIBILITY CODE REQUIRES A CLEARANCE OF 56" MINIMUM |
| | X 60 " MINIMUM. SHOW THE REQUIRED CLEARANCE ON THE |
| | FLOOR PLAN. |
| | 2) THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR SPACE |
| | REQUIRED FOR THE WATER CLOSET PER FAC SEC.603.2.3. SEE |
| | THE EXCEPTIONS FOR APPLICABILITY. |
| | 3) SHT. A-1 -THE ENLARGED FLOOR PLAN OF TOILET ROOM |
| | SHOWS THE TOILET ROOM DOOR SWINGING INTO THE ROOM AND |
| | THE FLOOR PLAN ON SHT. A-1 & A-2 SHOW THE DOOR SWINGING |
| | OUT. CLARIFY. |
| | 4) THE SINK IN THE COFFEE ROOM SHALL COMPLY WITH THE |
| | 2010 FAC SEC. 212.3 AND 606.2. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| | INSTA- HOT.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 6) SHT. A-1 NOTES THE WATER CLOEST IN THE COFFEE ROOM |
| | TO BE CAPPED BUT THE RISER DIAGRAM ON SHT. A-2 STATES |
| | "FUTURE WATER CLOSET." WHICH IS IT? |
| | 7) SHOW THE CLEAR FLOOR SPACE FOR THE SINK IN THE |
| | COFFEE ROOM PER THE 2010 FAC SEC.606.2. THE CLEAR FLOOR |
| | SPACE SHALL BE CENTERED ON THE FIXTURE, |
| | 8) THE SIZE OF THE VENT (2 1/2" ) FOR THE DRINKING |
| | FOUNTAIN AND SINK IS NOT A CONVENTIONAL PIPE SIZE. |
| | CLARIFY. |
| | 9) SUBMIT A WATER RISER FOR THE CHANGES MADE TO THE |
| | PLUMBING SYSTEM PER THE WPB AMEND, TO 2010 FBC SEC. |
| | 107.3.5.1.3. |
| | |