| Plan Review Notes For Permit 14101076 |
| Permit Number |
14101076 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-01 06:58:11 | 2008 NEC | | | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF | | | RE-INSPECTION FEE(S). | | | 1) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP | | | SURFACES ARE REQUIRED TO BE GFCI PROTECTED. | | | 2) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE | | | REQUIRED. | | | 3) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | | BRANCH CIRCUITS. | | | 4) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE | | | INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER | | | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2 | | | FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN | | | THAT SPACE. | | | 5) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE | | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | |
|