Plan Review Notes
Plan Review Notes For Permit 14101072
Permit Number 14101072
Review Stop G
Sequence Number 1
Notes
Date Text
2014-11-12 06:09:261) THE GAS SIZING TABLE THAT YOU HAVE REFERENCED ON THE
 GAS DRAWING IS FROM AN OUTDATED EDITION OF THE CODE.
 THIS TABLE NUMBER IN THE 2010 FL. GAS CODE IS FOR CSST,
 NOT PE. SUBMIT 2 COPIES OF THE CORRECT GAS SIZING TABLE
 FROM THE 2010 FGC WHICH IS THE CODE IN EFFECT, NOT THE
 2001 EDITION.
 2) SUBMIT 2 COPIES OF A CLEAR AND LEGIBLE PLAN OF THE
 DRAWING FROM AMERICAN WELDING & TANK CO. WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 3) SUBMIT 2 CLEAR AND LEGIBLE COPIES OF THE DRAWING
 FROM NFPA FOR THE TANK LOCATIONS. THE CODE EDITION IN
 EFFECT IS THE 2008 EDITION, NOT THE 1996 EDITION THAT
 YOU SUBMITTED. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 4) INDICATE THE DISTANCE OF THE LP TANK FROM THE
 DRIVEWAY. COMPLY WITH NFPA 58 SEC.6.6.6 .1 (D).
 5) SUBMIT TWO COPIES OF THE SIGNED AND SEALED DRAWINGS
 FOR THE AMERICAST SLAB. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 6) SUBMIT DOCUMENTATION THAT THE GENERATOR IS LISTED
 AND LABELED IN ACCORDANCE W/ 2010 FGC SEC. 301.3.
 7) STATIONARY GENERATORS SHALL MEET THE REQUIREMENTS OF
 UL 22OO PER THE 2010 FGC SEC.616.1.
  