| 2014-11-07 16:57:35 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE AMERICAST GENERATOR PADS ARE DESIGNED TO BE USED | | | WITH SPECIFIC GENERATOR MODELS. SUBMIT MANUFACTURER'S | | | SPECIFICATIONS WITH THE MODEL NUMBER AND OUTPUT | | | CAPACITY (KW) FOR THE GENERATOR THAT WILL BE INSTALLED. | | | FBC 107.2.1 | | | | | | 2) ONLY ONE SET OF DRAWINGS FOR THE AMERICAST GENERATOR | | | PAD WAS SUBMITTED. A MINIMUM OF TWO SETS ARE REQUIRED. | | | FBC 107.1 | | | | | | |
|