| 2014-12-07 08:48:45 | BUILDING PLAN REVIEW |
| | REVISION: 14101067 |
| | PERMIT: 14070014 |
| | ADD: 230 CLEMATIS ST. |
| | CONT: TWENTY TWO GROUP |
| | TEL: (772)528-7241 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SUN. DEC. 07/2014 |
| | ACTION: DENIED. |
| | |
| | 2A) ASK 2 & 3 BOTH OF THESE DETAILS ARE FOR A TYPICAL |
| | CHAIR DISPLAY. THESE SUBMITTED PLANS E2.1 NOW INDICATE |
| | WHERE THEY ARE TO BE INSTALLED WITHIN THE TENANT |
| | SEPARATION DEMISSING WAL WHICH IS A 1 HOUR TENANT |
| | SEPARATION WALL. PLEASE PROVIDE THE WALL ASSEMBLY THAT |
| | ALLOWS THE DRYWALL TO BE REMOVED FROM THE ASSEMBLY AND |
| | A METAL STUD OR PLATE INSERTED INTO THE CAVITY. |
| | 2010 FBC-B 709.1(6). / 709.3 FIRE-RESISTANCE RATING. |
| | FIRE PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF |
| | NOT LESS THAN 1 HOUR. |
| | 709.8 JOINTS. JOINTS MADE IN OR BETWEEN FIRE PARTITIONS |
| | SHALL COMPLY WITH SECTION 714. |
| | 714.1 GENERAL. JOINTS INSTALLED IN OR BETWEEN |
| | FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING |
| | ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL |
| | BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME |
| | PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE |
| | RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH |
| | IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE |
| | TESTED IN ACCORDANCE WITH SECTION 714.3. THE VOID |
| | CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY |
| | AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 714.4. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |