| Plan Review Notes For Permit 14101067 |
| Permit Number |
14101067 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-08 11:13:50 | 11/8/2014 | | | PROJECT: DWR WPB | | | PERMIT#: 14070014, REVISION#14101067 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW FOR REVISION#14101067 | | | ACTION: DENIED | | | | | | 1) THERE IS A LIGHT FIXTURE INDICATED ON THE SOFFIT | | | DETAIL BUT THERE ARE NO ELECTRICAL PLANS WITH THIS | | | SUBMITTAL. PLEASE PROVIDE AN ELECTRICAL PLAN INDICATING | | | THE PROPOSED WIRING MEATHOD, CIRCUIT AND CONTROL. WPB | | | AMENDMENTS TO THE FBC 107.3.2, FBC SECTIONS 505.2.1, | | | 505.2.2, 505.2.3 AND 505.2.4. | | | | | | 2) INDICATE MEATHOD OF BONDING METAL FRAMING MEMBERS. | | | FBC 2704. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|