| 2014-11-15 13:06:49 | 11/15/2014 |
| | PROJECT: COASTAL WAREHOUSE |
| | PERMIT#: 14101066 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE INFORMATION ON THE PLAN FOR THE METHODS AND |
| | MATERIALS PROPOSED FOR THE INSTALLATION OF THE SYSTEM. |
| | THE FLOOR PLAN INDICATE A CONNECTION FROM A FEW DEVICES |
| | TO OTHER DEVICES BUT DIAGRAM IS INCOMPLETE. PROVIDE A |
| | COMPLETE AND DETAILED PLAN OF THE INSTALLATION |
| | INCLUDING THE COMPLETE INTERCONNECTION BETWEEN DEVICES |
| | AND THE TERMINATION TO THE FACP ALL IN ACCORDANCE WITH |
| | THE REQUIREMENTS IN NEC 760. |
| | |
| | 2) PROVIDE THE LOCATION OF THE ELECTRICAL PANEL ON THE |
| | FLOOR PLAN ALONG WITH AN ELECTRICAL PANEL SCHEDULE |
| | INCLUDING THE FACP CIRCUIT INDICATING THAT IT WILL BE |
| | INSTALLED WITH A LOCK ON DEVICE AND BE IDENTIFIED WITH |
| | PERMANENT RED MARKING. |
| | |
| | 3) ALL INFORMATION ON THE PLANS INCLUDING THE |
| | SPECIFICATIONS AND MANUFACTURER PRODUCT INFORMATION |
| | DATA SHALL BE LEGIGBLE. THE BATTERY CALCULATIONS AND |
| | CIRCUIT DETAIL CHARTS ARE NOT LEGIBLE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |