 PROJECT: DOUBLETREE RENOVATION
 PERMIT#: 14101015
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) PROVIDE A LOAD CALCULATION FOR PANEL MDP. TOTAL
 CONNECTED LOAD IS NOT INDICATED AND HAS BEEN ALTERED
 DUE TO THE ADDING OF PANEL LC-1 AND LC-2. FBC 107.3.5
  
 2) PROVIDE A LOAD CALCULATION FOR PANEL LDP. TOTAL
 CONNECTED LOAD IS NOT INDICATED AND HAS BEEN ALTERED
 DUE TO THE ADDING OF PANEL LC-1 FROM PANEL LC. FBC
 107.3.5
  
 3) VERIFY 2000AMP MAIN IN PANEL MDP HAS GROUND FAULT
 PROTECTION. NEC 230.95
  
 4) VERIFY SIZE OF MAIN OCPD IN NEW PANEL LC-1.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  