| 2014-11-17 08:35:03 | BUILDING PLAN REVIEW |
| | PERMIT: 14101015 |
| | ADD: 1808 S. AUSTRALIAN AVE. |
| | CONT: ACCENT CONSTRUCTION SERVICES |
| | TEL: (941)270-1373 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. NOV. 17/2014 |
| | ACTION: DENIED |
| | |
| | 2ND REQUEST 1) THE TITLEBLOCK OF THE PLANS THE ARCHITEC |
| | OF RECORD HAS COPIED SIGNATURES NOT ORIGINALS. |
| | PLANS ARE TO BE SIGNED PERSONALLY WITH A FULL SIGNATURE |
| | FROM THE ARCHETECT OF RECORD PER 481.221 WITH A MINIMUM |
| | OF FIRST AND LAST NAME AS SHOWN ON THE ARCHITECTS' |
| | LICENSE, FAC 61G1-16.003 |
| | NOTICE: |
| | CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| | LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| | FEE TO THE DESIGNERS OF RECORD FOR PLAN REVIEW, IF |
| | PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED |
| | FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | |
| | |
| | |
| | 2) COMPLIED. |
| | THE D1.1 SHEET DEMOLITION NOTE # 5 INDICATES AN |
| | ALTERNATE BID,( NO EITHER / OR) FOR NEW AUTOMATIC |
| | SLIDDING ENTRY DOORS. PLEASE REVIEW 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. |
| | |
| | 3)SEMI- COMPLIED. THE TITLE PAGE DOES NOT LIST A LIFE |
| | SAFETY SHEET, SHEET A1.1 THE 1ST FLOOR RENOVATION PLANS |
| | INDICATE ROOM NUMBERS, USAGE OF ROOMS, THE PLANS DO NOT |
| | SHOW EGRESS ROUTES FROM THE ROOMS, NO OCCUPANT LOADS, |
| | FIRE SPRINKLERS, NO EMERGENCY LIGHTS NOR DIRECTIONAL OR |
| | EXIT LIGHTS. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | |
| | BUILDING TYPE; NOTE LISTED AS A IB (SHEET A0.1) |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | FIRE RATING OF WALLS - SHEET A1.1 LIST GUEST ROOM |
| | COORIDOR KEY NOTE # 1 AS A 1/2 HR FIRE RATED CORRIDOR. |
| | PLEASE REVIEW THE 2010 FBC-B 709.3 EXC. 2. 1/2 HOUR |
| | RATED COORIDORS ARE FOR BUILDING TYPE IIB, IIIB & VB. |
| | THIS BUILDING IS IDENTIFIED AS A TYPE IB. |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:EARLY WARNING |
| | SMOKE EVACUATION SYSTEMS/ SCHEMATIC FIRE SPRINKLERS |
| | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | LIGHT AND VENTILATION |
| | |
| | 4) 2ND REQUEST. THE A2.1 THE GUEST ROOM CORRIDOR DOES |
| | NOT SHOW AS A RATED CORRIDOR FBC-B TABLE 1018.1.- SHEET |
| | A1.1 LIST GUEST ROOM COORIDOR KEY NOTE # 1 AS A 1/2 HR |
| | FIRE RATED CORRIDOR. PLEASE REVIEW THE 2010 FBC-B 709.3 |
| | EXC. 2. 1/2 HOUR RATED COORIDORS ARE FOR BUILDING TYPE |
| | IIB, IIIB & VB. THIS BUILDING IS IDENTIFIED AS A TYPE |
| | IB. |
| | |
| | 5-8 ) COMPLIED. SHEET A2.1. THE GUEST ROOM CORRIDOOR |
| | DOOR # 1031 DOES NOT SHOW ON THE DOOR SCHEDULE AND |
| | SHOULD ALSO BE RATED FBC-B TABLE 715.4. |
| | |
| | 9) NEW COMMENT. SHEET A1.1 SHOWS (2) MEANS OF EGRESS |
| | FROM 1008, THE SQ. FT. OF THE ROOM IS 734 FT./ 15 = 49 |
| | OCCUPANTS. THIS ROOM WILL ONLY REQUIRE ONE EXIT. NOTE |
| | THE 2ND EXIT SHOWN WITH EXIT DIRECTIONAL LIGHT IS |
| | TAKING THE OCCUPANTS THROUGH THE STORAGE ROOM # 1008A. |
| | PLEASE REVIEW THE 2010 FBC-B 1014.2 EGRESS THROUGH |
| | INTERVENING SPACES. |
| | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| | THIS SECTION. |
| | 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| | |
| | 10) NEW COMMENT. FOYER TO BOARD ROOM DOES NOT SHOW FIRE |
| | SPRINKLERS, THERE ARE DOORS BETWEEN THE FOYER AND |
| | COORIDOR AND A DROPPED HEADER BETWEEN THE FOYER ITSELF |
| | AND THE BOARD ROOM. [F] 903.2.8 GROUP R. |
| | AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE |
| | WITH SECTION 903.3 SHALL BE PROVIDED THROUGHOUT ALL |
| | BUILDINGS WITH A GROUP R FIRE AREA. |
| | |
| | |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |