| 2014-11-07 11:52:46 | 11/7/2014 |
| | PROJECT: DOUBLETREE INTERIOR RENNOVATION |
| | PERMIT#: 14101015 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| | SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| | |
| | 2) PROVIDE AUTOMATIC LIGHTING CONTROL PER THE FBC 505.2 |
| | |
| | 3) PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH |
| | PROTECTION FOR THE SERVICE, PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 |
| | |
| | 4) PROVIDE AN ACTUAL LOAD CALCULATION IN ACCORDANCE |
| | WITH THE NEC ARTICLE 220. IF THE LOCAL UTILITY IS GOING |
| | TO BE REFFERENCED AS AN ALTERNATIVE TO A LOAD |
| | CALCULATION A LETTER FROM AN AUTHORIZED RERESENTITIVE |
| | OF THE LOCAL UTILITY WILL BE REQUIRED INDICATING A FULL |
| | 12 MONTHS OF USE. |
| | |
| | 5) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 |
| | REVISE OLANS TO INCLUDE A LIFE SAFETY PLAN TO DETERMINE |
| | THE REQUIRED EMERGENCY ILLUMINATION FOR THE MEANS OF |
| | EGRESS. |
| | A) THE BRANCH CIRCUIT FEEDING THE EMEGENCY /EXIT |
| | LIGHTING SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. THE BRANCH CIRCUIT THAT |
| | FEEDS EMERGENCY/EXIT LIGHTS SHALL BE CLEARLY IDENTIFIED |
| | AT THE DISTRIBUTION PANEL. |
| | |
| | 6A) WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE A |
| | FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE |
| | INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL |
| | NOT BE REDUCED. FBC 713.3.2 |
| | VERIFY FIRE RATED FLOORS AND WALLS PENETRATED BY |
| | ELECTRICAL OUTLETS CONDUITS OR CABLES SHALL BE "SHALL |
| | BE INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE |
| | WILL NOT BE REDUCED". FBC 713.3.2 |
| | B) PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR, |
| | FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A |
| | ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS |
| | 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL |
| | SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5. FBC |
| | 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | |
| | 7) PROVIDE MANUFACTURER DATA SHEETS FOR PROPOSED FLOOR |
| | BOXES TO INDICATE THE REQUIRED LISTING FOR THE |
| | EVIRONMENT IN WHICH THEY ARE INSTALLED. NEC110.3 FBC |
| | 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | |
| | 8) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| | TO FBC 107.2.1 |
| | |
| | A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | REQUIRED FOR FIRE ALARM, SECURITY, CCTV, ACCESS CONTROL |
| | SYSTEMS, AUDIO/VIDEO, ETC.. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |