| 2014-11-06 08:39:20 | BUILDING PLAN REVIEW |
| | PERMIT: 14101015 |
| | ADD: 1808 S. AUSTRALIAN AVE. |
| | CONT: ACCENT CONSTRUCTION SERVICES |
| | TEL: (941)270-1373 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. NOV. 05/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE TITLEBLOCK OF THE PLANS THE ARCHITEC OF RECORD |
| | HAS COPIED SIGNATURES NOT ORIGINALS. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | |
| | 2) THE D1.1 SHEET DEMOLITION NOTE # 5 INDICATES AN |
| | ALTERNATE BID,( NO EITHER / OR) FOR NEW AUTOMATIC |
| | SLIDDING ENTRY DOORS. PLEASE REVIEW 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. |
| | |
| | 3) THE TITLE PAGE DOES NOT LIST A LIFE SAFETY SHEET, |
| | SHEET A2.1 THE 1ST FLOOR RENOVATION PLANS INDICATE ROOM |
| | NUMBERS, USAGE OF ROOMS, THE PLANS DO NOT SHOW EGRESS |
| | ROUTES FROM THE ROOMS, NO OCCUPANT LOADS, FIRE |
| | SPRINKLERS, NO EMERGENCY LIGHTS NOR DIRECTIONAL OR EXIT |
| | LIGHTS. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | FIRE RATING OF WALLS |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:EARLY WARNING |
| | SMOKE EVACUATION SYSTEMS/ SCHEMATIC FIRE SPRINKLERS |
| | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | LIGHT AND VENTILATION |
| | |
| | 4) THE A2.1 THE GUEST ROOM CORRIDOR DOES NOT SHOW AS A |
| | RATED CORRIDOR FBC-B TABLE 1018.1. |
| | |
| | 5) SHEET A2.1. THE GUEST ROOM CORRIDOOR DOOR # 1031 |
| | DOES NOT SHOW ON THE DOOR SCHEDULE AND SHOULD ALSO BE |
| | RATED FBC-B TABLE 715.4. |
| | |
| | 6) SHEET A2.1 THE ELEVATOR EQUIPMENT ROOM AND DOOR ARE |
| | MISSING THE FIRE RATINS AS REQUIRED BY FBC-B 3006.4. |
| | |
| | 7) SHEET A.2.1 BOTH STAIRWELL 2 & 3 APPEAR TO BE IN THE |
| | WORK AREA ZONE OF WORK, THEY ARE 2 HR FIRE RATED WALLS |
| | WITH 1 1/2 OPENING PROTECTIVES FBC-B 1022.1. |
| | |
| | 8A) SHEET A2.1 THE PLANS SHOW A HOUSE LAUNDRY, FBC-B |
| | TABLE 508.2.5 DOES ALLOW FOR THE WALL TO BE SMOKE TIGHT |
| | CONSTRUCTION WHICH WILL REQUIRE COMPLIANCE WITH 711.4 |
| | CONTINUITY. |
| | |
| | 8B) NOTE THE LAUNDRY ROOM DOES NOT INDICATE IF THERE IS |
| | A LAUNDRY CHUTE THAT ENDS IN THIS ROOM, IF SO THIS ROOM |
| | IS THEN A TERMINATION ROOM AND WOULD NEED TO COMPLY |
| | WITH FBC-B 708.13.4. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |