 PROJECT: LOFT APTS
 PERMIT#: 14101000
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) GFP OF EQUIPMENT REQUIRED ON WYE ELECTRICAL SYSTEMS
 OF MORE THAN 150V TO GROUND AND NOT EXCEEDING 600VOLTS
 PHASE TO PHASE FOR EACH SERVICE DISCONNECT OVER
 1000AMPS. NEC230.95
  
 2) THE GROUND-FAULT PROTECTION SYSTEM SHALL BE
 PERFORMANCE TESTED WHEN FIRST INSTALLED ON SITE AND A
 RECORD OF THE TEST SHALL BE AVAILABLE FOR THE INSPECTOR
 ON SITE. NEC 230.95(C)
  
 3) THE LINE DIAGRAM INDICATE A 600AMP METER CAN AHEAD
 OF PANEL HDP. THERE ARE NO METER CAN APPROVED FOR
 600AMPS. REVISE PLANS ACCORDINGLY.
  
 4) VERIFY THE FIRE PUMP FEEDERS, CIRCUIT CONDUCTORS,
 AND PUMP WIRING ARE APPROPRIATELY FIRE PROTECTED.
 INDICATE THE FIRE RATING AND MATERIAL PROPSED. NEC
 695.6, 695.14
  
 5) VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING
 NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR,
 PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE
 ACCESSORIES. VERIFY THE MAXIMUM VOLTAGE DROP IS NOT
 MORE THAN 15 % BELOW NORMAL STARTING AND 5% BELOW WHEN
 THE MOTOR IS OPERATING AT 115% OF THE FULL LOAD CURRENT
 RATING. NEC 695.6, 695.7
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,