| Plan Review Notes For Permit 14101000 |
| Permit Number |
14101000 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-20 13:53:34 | 11/20/2014 | | | PROJECT: LOFT APTS | | | PERMIT#: 14101000 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) GFP OF EQUIPMENT REQUIRED ON WYE ELECTRICAL SYSTEMS | | | OF MORE THAN 150V TO GROUND AND NOT EXCEEDING 600VOLTS | | | PHASE TO PHASE FOR EACH SERVICE DISCONNECT OVER | | | 1000AMPS. NEC230.95 | | | | | | 2) THE GROUND-FAULT PROTECTION SYSTEM SHALL BE | | | PERFORMANCE TESTED WHEN FIRST INSTALLED ON SITE AND A | | | RECORD OF THE TEST SHALL BE AVAILABLE FOR THE INSPECTOR | | | ON SITE. NEC 230.95(C) | | | | | | 3) THE LINE DIAGRAM INDICATE A 600AMP METER CAN AHEAD | | | OF PANEL HDP. THERE ARE NO METER CAN APPROVED FOR | | | 600AMPS. REVISE PLANS ACCORDINGLY. | | | | | | 4) VERIFY THE FIRE PUMP FEEDERS, CIRCUIT CONDUCTORS, | | | AND PUMP WIRING ARE APPROPRIATELY FIRE PROTECTED. | | | INDICATE THE FIRE RATING AND MATERIAL PROPSED. NEC | | | 695.6, 695.14 | | | | | | 5) VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING | | | NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR, | | | PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE | | | ACCESSORIES. VERIFY THE MAXIMUM VOLTAGE DROP IS NOT | | | MORE THAN 15 % BELOW NORMAL STARTING AND 5% BELOW WHEN | | | THE MOTOR IS OPERATING AT 115% OF THE FULL LOAD CURRENT | | | RATING. NEC 695.6, 695.7 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|