| Plan Review Notes For Permit 14100982 |
| Permit Number |
14100982 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-30 16:36:36 | ROOF RECOVER BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- REVISE THE RAS 117 CALCULATIONS SUBMITTED. THE | | | ENGINEER NEEDS TO UTILIZE THE WITHDRAWAL RESISTANCE | | | VALUE TAKEN FROM THE TESTING APPLICATION STANDARD (TAS | | | 105) AS REQUIRED BY LIMITATION #5.4 FROM FLORIDA | | | PRODUCT APPROVAL FL16440-R2 SUBMITTED. SEC. 1609 OF | | | 2010 FBC. | | | | | | 2- RECOVER INSTALLATIONS REQUIRES AN INSPECTION OF THE | | | EXISTING ROOF AS REQUIRED BY LIMITATION #5.6 OF FLORIDA | | | PRODUCT APPROVAL FL16440-R2. ALSO, CITY OF WEST PALM | | | BEACH REQUIRES A BUILDING PRE-INSPECTION (INSPECTION | | | CODE 101) ONCE THE PERMIT IS ISSUED AND BEFORE ANY WORK | | | IS DONE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|