Plan Review Notes
Plan Review Notes For Permit 14100982
Permit Number 14100982
Review Stop B
Sequence Number 1
Notes
Date Text
2014-10-30 16:36:36ROOF RECOVER BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE THE RAS 117 CALCULATIONS SUBMITTED. THE
 ENGINEER NEEDS TO UTILIZE THE WITHDRAWAL RESISTANCE
 VALUE TAKEN FROM THE TESTING APPLICATION STANDARD (TAS
 105) AS REQUIRED BY LIMITATION #5.4 FROM FLORIDA
 PRODUCT APPROVAL FL16440-R2 SUBMITTED. SEC. 1609 OF
 2010 FBC.
  
 2- RECOVER INSTALLATIONS REQUIRES AN INSPECTION OF THE
 EXISTING ROOF AS REQUIRED BY LIMITATION #5.6 OF FLORIDA
 PRODUCT APPROVAL FL16440-R2. ALSO, CITY OF WEST PALM
 BEACH REQUIRES A BUILDING PRE-INSPECTION (INSPECTION
 CODE 101) ONCE THE PERMIT IS ISSUED AND BEFORE ANY WORK
 IS DONE.
  