| Plan Review Notes For Permit 14100967 |
| Permit Number |
14100967 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-30 10:46:35 | 10/30/2014 | | | PROJECT: RESIDENTIAL RENNOVATION | | | PERMIT#: 14100967 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE ELECTRICAL PLANS OF SUFFICIENT DETAIL AND | | | CLAIRITY.FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH | | | WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. | | | COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW | | | CIRCUITS ON FLOOR PLAN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|