| Plan Review Notes For Permit 14100912 |
| Permit Number |
14100912 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-29 13:06:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE SUBMITTED PLANS WERE TOO SMALL AND UNREADABLE. | | | | | | THE LOCATION OF EACH OF THE ACCESS SYSTEMS WERE | | | UNDETERMINABLE. | | | | | | ACCESS CONTROL DEVICES WERE NOT INDICATED. | | | | | | ACCESS CONTROL SEQUENCING WAS NOT INDICATED TO ENSURE | | | COMPLIANCE WITH THE EXITING REQUIREMENTS OF NFPA 101, | | | CHAPTER 7. |
|