2014-10-28 13:19:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PROVIDED INFORMATION INDICATES THAT THE
 INSTALLATION MAY NOT COMPLY WITH NFPA 13 LIGHT OR
 ORDINARY HAZARD OCCUPANCY. PLEASE RE-WORD TO CLARIFY.
  
 PLEASE PROVIDE THE HYDRALIC CALCULATIONS FOR THE
 PROPOSED INSTALLATION AND THAT THE SYSTEM COMPLIES WITH
 NFPA 13 FOR LIGHT HAZARD OCCUPANCY.
  
 IT APPEARS THAT A DROP CEILING IS PROPOSED; HOWEVER,
 THE SIDE VIEW DOES NOT SHOW IT. PLEASE INDICATE THAT A
 DROP CEILING IS BEING INSTALLED AND A DIAGRAM
 ILLUSTRATING PIPING TO THE HEADS.