| Plan Review Notes For Permit 14100852 |
| Permit Number |
14100852 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-28 13:19:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE PROVIDED INFORMATION INDICATES THAT THE | | | INSTALLATION MAY NOT COMPLY WITH NFPA 13 LIGHT OR | | | ORDINARY HAZARD OCCUPANCY. PLEASE RE-WORD TO CLARIFY. | | | | | | PLEASE PROVIDE THE HYDRALIC CALCULATIONS FOR THE | | | PROPOSED INSTALLATION AND THAT THE SYSTEM COMPLIES WITH | | | NFPA 13 FOR LIGHT HAZARD OCCUPANCY. | | | | | | IT APPEARS THAT A DROP CEILING IS PROPOSED; HOWEVER, | | | THE SIDE VIEW DOES NOT SHOW IT. PLEASE INDICATE THAT A | | | DROP CEILING IS BEING INSTALLED AND A DIAGRAM | | | ILLUSTRATING PIPING TO THE HEADS. |
|