| 2014-11-14 16:32:28 | 11/14/2014 |
| | PROJECT: BEDROOM WALL |
| | PERMIT#: 14100830 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) MINIMUM ELECTRICAL PLAN REVIEW CRITERIA SHALL |
| | INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: WIRING, |
| | SERVICES, FEEDERS AND BRANCH CIRCUITS, OVERCURRENT |
| | PROTECTION, GFCIS, GROUNDING, WIRING METHODS AND |
| | MATERIALS, WPB AMENDMENTS TO FBC 107.3.5.1.2 |
| | |
| | 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | WPB AMENDMENTS TO FBC 107.2.1 |
| | |
| | 3) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315 |
| | |
| | 4) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| | SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| | OUTLET. 210.52(A)(1) |
| | |
| | 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |