Plan Review Notes
Plan Review Notes For Permit 14100821
Permit Number 14100821
Review Stop E
Sequence Number 1
Notes
Date Text
2014-11-03 15:36:1911/3/2014
 PROJECT: CAFE REMODEL
 PERMIT#: 14100821
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A LOAD CALCULATION FOR THE NEW PANEL "K" AND
 FOR THE ELECTRICAL SERVICE THAT FEEDS IT.
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) PROVIDE THE DESCRIPTION FOR THE SYMBOL THAT IS A
 SQUARE WITH THE LETTER T INSIDE IT. ASSUMING IT IS FOR
 A TELEVISION CATV OUTLET PROVIDE ADDITIONAL DETAILED
 INFORMATION ABOUT WHAT IT PROPSED TO FEED THESE OUTLET
 LOCATIONS AND FROM WHERE
  
 4) PROVIDE MORE DETAILED INFORMATION FOR THE CIRCUITS
 THAT ARE BEING DEMO'D IN CAFE AREA.
  
 5) PROVIDE MORE DETAILED INFORMATION FOR THE CIRCUITS
 ASSOCIATED WITH AND UNDER THE HOOD. THERE ARE SHUNT
 TRIP CIRCUITS IDENTIFIED IN THE PANEL SCHEDULE "K"
 PROVIDE ADDITIONAL INFORMATION ON HOW AND WHAT IS
 PROPOSED TO FEED AND TRIP THE SHUNT TRIP CIRCUIT
 BREAKERS. CLARIFY THE USE OF CIRCUIT K5 AND K7
  
 6) PROVIDE MORE DETAILED INFORMATION ON THE ELECTRICAL
 PLANS AN THE RELOCATED WATER HEATER. IDENTIFY THE
 CIRCUIT FEEDING IT ON THE FLOOR PLAN AND PANELSCHEDULE.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR HOOD, FIRE SUPRESSION SYSTEM.
 SECURITY, CCTV, AUDIO VIDEO, AND NETWORK, COMMUNICATION
 AND POS..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  