| Date |
Text |
| 2014-11-03 15:36:19 | 11/3/2014 |
| | PROJECT: CAFE REMODEL |
| | PERMIT#: 14100821 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A LOAD CALCULATION FOR THE NEW PANEL "K" AND |
| | FOR THE ELECTRICAL SERVICE THAT FEEDS IT. |
| | |
| | 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 3) PROVIDE THE DESCRIPTION FOR THE SYMBOL THAT IS A |
| | SQUARE WITH THE LETTER T INSIDE IT. ASSUMING IT IS FOR |
| | A TELEVISION CATV OUTLET PROVIDE ADDITIONAL DETAILED |
| | INFORMATION ABOUT WHAT IT PROPSED TO FEED THESE OUTLET |
| | LOCATIONS AND FROM WHERE |
| | |
| | 4) PROVIDE MORE DETAILED INFORMATION FOR THE CIRCUITS |
| | THAT ARE BEING DEMO'D IN CAFE AREA. |
| | |
| | 5) PROVIDE MORE DETAILED INFORMATION FOR THE CIRCUITS |
| | ASSOCIATED WITH AND UNDER THE HOOD. THERE ARE SHUNT |
| | TRIP CIRCUITS IDENTIFIED IN THE PANEL SCHEDULE "K" |
| | PROVIDE ADDITIONAL INFORMATION ON HOW AND WHAT IS |
| | PROPOSED TO FEED AND TRIP THE SHUNT TRIP CIRCUIT |
| | BREAKERS. CLARIFY THE USE OF CIRCUIT K5 AND K7 |
| | |
| | 6) PROVIDE MORE DETAILED INFORMATION ON THE ELECTRICAL |
| | PLANS AN THE RELOCATED WATER HEATER. IDENTIFY THE |
| | CIRCUIT FEEDING IT ON THE FLOOR PLAN AND PANELSCHEDULE. |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR HOOD, FIRE SUPRESSION SYSTEM. |
| | SECURITY, CCTV, AUDIO VIDEO, AND NETWORK, COMMUNICATION |
| | AND POS.. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |