 PROJECT: 533 CLEMATIS
 PERMIT#: 14100819
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE PANEL SCHEDULE FOR PANEL KI AND MDP CIRCUITS
 IN OFFICE AS BATHROOM AND LOAD CALCULATION AND THERE IS
 NO CIRCUIT IN MDP INDICATED FOR SUB-PANEL K2.. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4 REVISE PANEL SCHEDULE AND
 LOAD CALCULATION FOR PANEL MDP.
  
 2) REVISE RISER DIAGRAM FOR CLARITY AND ACCURACY. THE
 RISER DIAGRAM INDICATE A 250AMP PANEL K1 BEING FED FROM
 PANEL MDP WITH 4, #4/0 AND 1,#8 #6 AND A 225AMP PANEL
 K2 BEING FED FROM PANEL MDP WITH 4,#3 AND 1,#8. NONE OF
 THIS IS ADAQUATE TO SUPPORT THE LOAD PROPOSED TO BE
 FED. NEC 310.16
  
 3) CLARIFY THE SCOPE OF WORK. THE DESCRIPTION OF WORK
 ON THE APPLICATION AND ON THE PLAN ARE CONFLICTING.
 CLARIFY WHAT THE ACTUAL SCOPE OF WORK IS AND WHAT IS
 EXISTING TO REMAIN, WHAT IS PROPOSED TO RENOVATED AND
 WHAT IS TO BE INSTALLED NEW.
  
 4) THE RISER DIAGRAM ON SHEET 2.1E STATES "ALL APNELS
 AND SERVICES ARE EXISTING" YET THE RISER DIAGRAM ITSELF
 INDICATES A NEW SERVICE FOR THE RESTAURANT. A NEW
 400AMP MAIN, FEEDER MDP, K1 & K2,
  
 5) THERE IS REFERENCE TO NOTES ON SHEET 2.1E BUT THERE
 ARE NO NOTES. THERE ARE ALSO TWO SHEETS #2.1E CLARIFY.
  
 6) THERE IS A REFLECTED CEILING PLAN BUT THERE IS NO
 ELECTRICAL LIGHTING PLAN. PROVIDE ELECTRICAL LIGHTING
 PLANS INDICATING HOW THE LIGHTING IS PROPOSED TO BE
 CONTROLED. CLARIFY
  
 THERE IS A NOTE ON SHEET 2.1E THAT STATES
 "RECIRCULATING PUMPS CEILING SPACE MOUNTED" BUT THERE
 IS NO CIRCUITRY OR CONTROLS INVOLOVING ANY
 RECIRCULATING PUMPS. CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  