| 2014-10-28 18:29:14 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | MECHANICAL REVISION IS DENIED |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR |
| | THE THE NEW A/C UNITS AS REQUIRED BY FBCR M1401.3. |
| | |
| | 2) SUBMIT AHRI CERTIFICATIONS FOR THE NEW HEATING AND |
| | COOLING EQUIPMENT. FBC ENERGY CONSERVATION SECTION |
| | 402.1.2.4. |
| | |
| | 3) REVISE THE SIZE OF THE THROUGH THE WALL TRANSFER |
| | GRILL AT THE GUEST BEDROOM TO COMPLY WITH FBCR M1602.4 |
| | FOR BALANCED RETURN AIR. |
| | TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF GRILL |
| | AREA TO 100 CFMS OF SUPPLY AIR. THERE IS 400 CFMS |
| | SUPPLIED TO THE SECOND FLOOR GUEST BEDROOM. 50 SQUARE |
| | INCHES TIMES 4 EQUALS 200 SQUARE INCHES OF TRANSFER |
| | GRILL AREA REQUIRED. 14 X 6 EQUALS 84 SQUARE INCHES OF |
| | TRANSFER GRILL AREA PROVIDED. ADDITION RETURN AREA IS |
| | REQUIRED. |
| | |
| | 4) PROVIDE TWO SETS OF AN EQUIPMENT ANCHORING DETAIL |
| | FOR THE MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND |
| | LOADS. FBCR M1307.2.1 |
| | |
| | 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. THE TITLE BLOCK |
| | ON THE PLANS HAVE THE NAME OF A FLORIDA LICENSED |
| | ARCHITECT WHO IS REQUIRED TO SIGN AND SEAL THE PLANS |
| | PER CHAPTER 481, FLORIDA STATUTES & 61G1 FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | |
| | |