| 2014-10-28 08:02:23 | BUILDING REVIEW COMMENTS TO SUBMITTAL ADDRESSING |
| | PROVISO DATED 8/7/14: |
| | |
| | 1- COMMENT #1: |
| | (A) OK. NO ROOF WORK. |
| | |
| | (B) NOT OK. SEE COMMENTS BELOW: |
| | (1) DRAWING S-100 SUBMITTED NEEDS ENGINEER ORIGINAL |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST. |
| | (2) FLORIDA PRODUCT APPROVAL FL 474 SPECIFIED ON THE |
| | CONNECTOR'S SCHEDULE ON SHEET S-100 IS NOT CURRENT. |
| | NEED PRODUCT APPROVAL NUMBER FOR CURRENT CODE EDITION |
| | 2010 FBC. ALSO, THERE IS NOT FLORIDA PRODUCT APPROVAL |
| | NUMBER OR NOA NUMBER FOR TSP CONNECTOR. REVISE AS |
| | REQUIRED. |
| | |
| | (C) OK. CURRENT MULLION NOA SUBMITTED. |
| | |
| | (D) OK. ROUND CASEMENT WINDOW SUBMITTED WITH FIXED |
| | CASEMENT WINDOW NOA. |
| | |
| | (E) OK. |
| | |
| | (F) OK. |
| | |
| | 2- NOT OK. ALL PRODUCT APPROVALS NEED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. THE |
| | ONLY PRODUCT APPROVAL THAT WAS SUBMITTED AT HIS TIME |
| | WAS THE WINDOW MULLIONS AND WAS NOT REVIEWED BY THE |
| | DESIGNER OF RECORD. |
| | |
| | 3- ITEM #3. ACCORDING TO CONTRACTOR'S RE-SUBMITTAL |
| | LETTER, CONTRACTOR WILL DELIVER DRAWINGS/SPECS THE WEEK |
| | OF 10/27/14. NOT SUBMITTED YET. |
| | |
| | 4- BALCONY GUARDRAILS DETAILS SUBMITTED NEED THE |
| | FOLLOWING: |
| | A) PROVIDE THE DESIGN INFORMATION AS REQUIRED BY TABLE |
| | R301.5 OF 2010 FBC. |
| | B) PROVIDE THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 |
| | OF CITY AMENDMENTS TO FBC. |
| | C) DESIGNER OF RECORD TO REVIEW AND APPROVE THE BALCONY |
| | GUARDRAILS DRAWINGS PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 5- ENGINEER RESPONSIBLE FOR SHEET S-100 TO PROVIDE |
| | ORIGINAL SIGNATURE AS REQUIRED BY CHAPTER 471 F. ST. |
| | |
| | 6- NOT OK. THERE WERE NO REVISED STRUCTURAL BUCK |
| | DETAILS SUBMITTED. SEC. R612.10.2.1 OF 2010 FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | SEE ORIGINAL PROVISO COMMENTS BELOW FOR REFERENCE: |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| | ON PLANS, DETAILS AND SPECIFICATIONS. |
| | C) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. |
| | D) ROUND CASEMENT WINDOW AS SHOWN ON PLANS. |
| | E) NEW ALUMINUM CASEMENT NOA 12-0216.04 WAS SUBMITTED. |
| | NEED TO PROVIDE TWO COPIES. |
| | F) NEW FRENCH DOORS FLORIDA PRODUCT APPROVAL FL14504 |
| | WAS SUBMITTED. NEED TO PROVIDE TWO COPIES. |
| | 2- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT |
| | APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS. |
| | 3- SHEET A-2: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR INTERIOR HANDRAIL TO BE REPLACED. |
| | TABLE R301.5 AND SEC. R311.7.7. |
| | 4- SHEET A-4: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR NEW MASTER BATHROOM BALCONY. TABLE |
| | R301.5 AND SEC. R312. |
| | 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR NEW ARCHED OPENINGS IN THE REBUILT DEN AREA ON |
| | FIRST FLOOR. SEC. R301. |
| | 6- SHEET A-9: REVISE ALL THE DOOR STRUCTURAL BUCK |
| | DETAILS. BUCK NEED TO PROVIDE FULL SUPPORT TO THE DOOR |
| | FRAME. SEC. R612.10.2.1. |