| Plan Review Notes For Permit 14100783 |
| Permit Number |
14100783 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-12-17 07:57:23 | 1.) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. NEC 700.12(F) | | | | | | 2.) OUTLETS INSTALLED OUTDOORS OR WITHIN 6' OF A SINK | | | SHALL BE GFCI PROTECTED. NEC 210.8(B)(4) | | | A.) GFI OUTLETS INSTALLED IN DAMP OR WET LOCATIONS | | | SHALL ALSO BE THE WEATHER RESISTANT TYPE. NEC | | | 406.8(B)(1) |
|