| Date |
Text |
| 2014-11-04 13:23:42 | 1) A UNISEX TOILET ROOM IS REQUIRED PER 2010 FPC |
| | SEC.403.5. |
| | 2) THE PLANS REFERENCE THE 2007 FBC IN SEVERAL AREAS. |
| | ENSURE THAT REFERENCES TO THE BUILDING CODE ARE BASED |
| | ON THE 2010 EDITION OF THE FBC. |
| | 3) SHT. A3.01 - DETAIL #4 - THE DRINKING FOUNTAINS |
| | SHALL HAVE A FORWARD APPROACH PER THE FAC SEC.602.2. |
| | 4) SHT.MP 1.01 - FIXTURES P-3, P-5, P-7, P-8, ARE NOT |
| | VENTED.FPC SEC.901.2, 901.2.1. |
| | 5)) CLEANOUTS ARE REQD. IN STACKS PER 2010 FPC |
| | SEC.708.3.4. |
| | 7) FIXTURE P2A IN WOMEN'S RESTROOM NOT VENTED. FPC SEC. |
| | 901.2. |
| | 8) THE PLUMBING SYSTEM AS DESINED IS NOT CODE |
| | COMPLIANT. PLEASE REFER TO SEC. 911 OF THE FLORIDA |
| | PLUMBING CODE FOR A CIRCUIT VENTING SYSTEM. |
| | 9) SIZE THE HORIZONTAL DRAIN FOR THE URINALS AND FOR |
| | P-5 FIXTURE, WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 10) SHOW THE LOCATION OF THE WATER HEATER ON THE FLOOR |
| | PLAN. |
| | 11) THE LAYOUT OF THE FIXTURES ON THE SANITARY RISER |
| | AND THE WATER RISER DO NOT MATCH THE FLOOR PLAN. WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 12) THE TERMINATION OF THE PAN DRAIN SHALL COMPLY W/ |
| | 2010 FPC SEC.504.7.2 |
| | 13) SHUT-OFF VALVES ARE REQUIRED IN THE WATER PIPE |
| | SYSTEM PER THE 2010 FPC. SEC. 606.1. |
| | 14) SHT. MP1.01 - THE PLANS SHOW THE NAME OF PLUMBING |
| | FIXTURE P-3 IN THE WOMEN'S RESTROOM BY THE ACCESSIBLE |
| | STALL DOOR IN THE LADIES RESTROOM. CLARIFY/ REMOVE. |