2014-11-04 13:23:421) A UNISEX TOILET ROOM IS REQUIRED PER 2010 FPC
 SEC.403.5.
 2) THE PLANS REFERENCE THE 2007 FBC IN SEVERAL AREAS.
 ENSURE THAT REFERENCES TO THE BUILDING CODE ARE BASED
 ON THE 2010 EDITION OF THE FBC.
 3) SHT. A3.01 - DETAIL #4 - THE DRINKING FOUNTAINS
 SHALL HAVE A FORWARD APPROACH PER THE FAC SEC.602.2.
 4) SHT.MP 1.01 - FIXTURES P-3, P-5, P-7, P-8, ARE NOT
 VENTED.FPC SEC.901.2, 901.2.1.
 5)) CLEANOUTS ARE REQD. IN STACKS PER 2010 FPC
 SEC.708.3.4.
 7) FIXTURE P2A IN WOMEN'S RESTROOM NOT VENTED. FPC SEC.
 901.2.
 8) THE PLUMBING SYSTEM AS DESINED IS NOT CODE
 COMPLIANT. PLEASE REFER TO SEC. 911 OF THE FLORIDA
 PLUMBING CODE FOR A CIRCUIT VENTING SYSTEM.
 9) SIZE THE HORIZONTAL DRAIN FOR THE URINALS AND FOR
 P-5 FIXTURE, WPB AMEND. TO 2010 FBC SEC.107.2.1.
 10) SHOW THE LOCATION OF THE WATER HEATER ON THE FLOOR
 PLAN.
 11) THE LAYOUT OF THE FIXTURES ON THE SANITARY RISER
 AND THE WATER RISER DO NOT MATCH THE FLOOR PLAN. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 12) THE TERMINATION OF THE PAN DRAIN SHALL COMPLY W/
 2010 FPC SEC.504.7.2
 13) SHUT-OFF VALVES ARE REQUIRED IN THE WATER PIPE
 SYSTEM PER THE 2010 FPC. SEC. 606.1.
 14) SHT. MP1.01 - THE PLANS SHOW THE NAME OF PLUMBING
 FIXTURE P-3 IN THE WOMEN'S RESTROOM BY THE ACCESSIBLE
 STALL DOOR IN THE LADIES RESTROOM. CLARIFY/ REMOVE.