Plan Review Notes
Plan Review Notes For Permit 14100745
Permit Number 14100745
Review Stop M
Sequence Number 1
Notes
Date Text
2014-12-01 14:33:40PLEASE REVIEW ALL CODES CONCERNING FBC - MECHANICAL
 SPECIFICALY CHAPTERS 3, 4, AND DETAIL ON MECHANICAL
 PLANS:
  
  
 301.12 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING
  
  
 301.15 NFPA STANDARDS.
 UNLESS OTHERWISE SPECIFIED IN THIS CODE, AIR
 CONDITIONING EQUIPMENT SHALL COMPLY WITH THE FOLLOWING
 STANDARDS:
  
 1. NFPA 90A (STANDARD FOR THE INSTALLATION OF AIR
 CONDITIONING AND VENTILATING SYSTEMS).
  
 2. NFPA 90B (STANDARD FOR THE INSTALLATION OF WARM AIR
 HEATING AND AIR CONDITIONING SYSTEMS).
  
 306.1 ACCESS FOR MAINTENANCE AND REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT DISABLING THE FUNCTION
 OF A FIRE-RESISTANCE-RATED ASSEMBLY OR REMOVING
 PERMANENT CONSTRUCTION, OTHER APPLIANCES, VENTING
 SYSTEMS OR ANY OTHER PIPING OR DUCTS NOT CONNECTED TO
 THE APPLIANCE BEING INSPECTED, SERVICED, REPAIRED OR
 REPLACED. A LEVEL WORKING SPACE AT LEAST 30 INCHES DEEP
 AND 30 INCHES WIDE (762 MM BY 762 MM) SHALL BE PROVIDED
 IN FRONT OF THE CONTROL SIDE TO SERVICE AN APPLIANCE.
  
 306.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO
 ALLOW REMOVAL OF THE LARGEST APPLIANCE. THE PASSAGEWAY
 SHALL NOT BE LESS THAN 30 INCHES (762 MM) HIGH AND 22
 INCHES (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM)
 IN LENGTH MEASURED ALONG THE CENTERLINE OF THE
 PASSAGEWAY FROM THE OPENING TO THE APPLIANCE. THE
 PASSAGEWAY SHALL HAVE CONTINUOUS SOLID FLOORING NOT
 LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30
 INCHES (762 MM) WIDE SHALL BE PRESENT AT THE FRONT OR
 SERVICE SIDE OF THE APPLIANCE. THE CLEAR ACCESS OPENING
 DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES
 (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL
 OF THE LARGEST APPLIANCE.
  
 306.3.1 ELECTRICAL REQUIREMENTS.
 A LIGHTING FIXTURE WITH RECEPTACLE OUTLET, CONTROLLED
 BY A SWITCH LOCATED AT THE PASSAGEWAY OPENING, SHALL BE
 PROVIDED SO AS TO LIGHT THE PASSAGEWAY AND SERVICE AREA
 AND INSTALLED IN ACCORDANCE WITH CHAPTER 27 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 306.3.2 AIR HANDLING UNITS.
 AIR HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
  
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 SIX (6) FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
  
 A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER,
 EFFICIENT, AND ECONOMIC OPERATION OF THE AIR
 CONDITIONING SYSTEM, YOU MUST ENSURE THAT REGULAR
 MAINTENANCE IS PERFORMED.
  
 YOUR AIR CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: 1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 306.4.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE PROVIDED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 27 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 307.2.1 CONDENSATE DISPOSAL.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN ONE-EIGHTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (1-PERCENT SLOPE). CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE.
  
 307.2.3 AUXILIARY AND SECONDARY DRAIN SYSTEMS.
 IN ADDITION TO THE REQUIREMENTS OF SECTION 307.2.1,
 WHERE DAMAGE TO ANY BUILDING COMPONENTS COULD OCCUR AS
 A RESULT OF OVERFLOW FROM THE EQUIPMENT PRIMARY
 CONDENSATE REMOVAL SYSTEM, ONE OF THE FOLLOWING
 AUXILIARY PROTECTION METHODS SHALL BE PROVIDED FOR EACH
 COOLING COIL OR FUEL-FIRED APPLIANCE THAT PRODUCES
 CONDENSATE:
  
 1. AN AUXILIARY DRAIN PAN WITH A SEPARATE DRAIN SHALL
 BE PROVIDED UNDER THE COILS ON WHICH CONDENSATION WILL
 OCCUR. THE AUXILIARY PAN DRAIN SHALL DISCHARGE TO A
 CONSPICUOUS POINT OF DISPOSAL TO ALERT OCCUPANTS IN THE
 EVENT OF A STOPPAGE OF THE PRIMARY DRAIN. THE PAN SHALL
 HAVE A MINIMUM DEPTH OF 11/2INCHES (38 MM), SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) LARGER THAN THE UNIT OR
 THE COIL DIMENSIONS IN WIDTH AND LENGTH AND SHALL BE
 CONSTRUCTED OF CORROSION-RESISTANT MATERIAL. GALVANIZED
 SHEET STEEL PANS SHALL HAVE A MINIMUM THICKNESS OF NOT
 LESS THAN 0.0236 INCH (0.6010 MM) (NO. 24 GAGE).
 NONMETALLIC PANS SHALL HAVE A MINIMUM THICKNESS OF NOT
 LESS THAN 0.0625 INCH (1.6 MM).
  
 2. A SEPARATE OVERFLOW DRAIN LINE SHALL BE CONNECTED TO
 THE DRAIN PAN PROVIDED WITH THE EQUIPMENT. SUCH
 OVERFLOW DRAIN SHALL DISCHARGE TO A CONSPICUOUS POINT
 OF DISPOSAL TO ALERT OCCUPANTS IN THE EVENT OF A
 STOPPAGE OF THE PRIMARY DRAIN. THE OVERFLOW DRAIN LINE
 SHALL CONNECT TO THE DRAIN PAN AT A HIGHER LEVEL THAN
 THE PRIMARY DRAIN CONNECTION.
  
 AS AN ALTERNATIVE TO A SEPARATE DRAIN LINE, A
 WATER-LEVEL DETECTION DEVICE THAT WILL SHUT OFF THE
 EQUIPMENT SERVED PRIOR TO OVERFLOW OF THE PAN SHALL BE
 PROVIDED. THE WATER LEVEL DETECTION DEVICE SHALL
 CONNECT TO THE DRAIN PAN AT A HIGHER LEVEL THAN THE
 PRIMARY DRAIN CONNECTION.
  
 3. AN AUXILIARY DRAIN PAN WITHOUT A SEPARATE DRAIN LINE
 SHALL BE PROVIDED UNDER THE COILS ON WHICH CONDENSATE
 WILL OCCUR. SUCH PAN SHALL BE EQUIPPED WITH A
 WATER-LEVEL DETECTION DEVICE CONFORMING TO UL 508 THAT
 WILL SHUT OFF THE EQUIPMENT SERVED PRIOR TO OVERFLOW OF
 THE PAN. THE AUXILIARY DRAIN PAN SHALL BE CONSTRUCTED
 IN ACCORDANCE WITH ITEM 1 OF THIS SECTION.
  
 401.2 VENTILATION REQUIRED.
 EVERY OCCUPIED SPACE SHALL BE VENTILATED BY NATURAL
 MEANS IN ACCORDANCE WITH SECTION 402 OR BY MECHANICAL
 MEANS IN ACCORDANCE WITH SECTION 403.
  
 IN LIEU OF COMPLIANCE WITH SECTION 403.1 THROUGH
 SECTION 403.3, MECHANICAL VENTILATION MAY BE
 IMPLEMENTED IN COMPLIANCE WITH ASHRAE 62.1.
  
 401.3 WHEN REQUIRED.
 VENTILATION SHALL BE PROVIDED DURING THE PERIODS THAT
 THE ROOM OR SPACE IS OCCUPIED.
  
 401.4 INTAKE OPENING LOCATION.
 AIR INTAKE OPENINGS SHALL COMPLY WITH ALL OF THE
 FOLLOWING:
  
 1. INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10
 FEET (3048 MM) FROM LOT LINES OR BUILDINGS ON THE SAME
 LOT. WHERE OPENINGS FRONT ON A STREET OR PUBLIC WAY,
 THE DISTANCE SHALL BE MEASURED TO THE CENTERLINE OF THE
 STREET OR PUBLIC WAY.
  
 2. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM)
 HORIZONTALLY FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT
 SOURCE, SUCH AS VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS, EXCEPT AS SPECIFIED IN ITEM 3 OR
 SECTION 501.2.1.
  
 3. INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 3
 FEET (914 MM) BELOW CONTAMINANT SOURCES WHERE SUCH
 SOURCES ARE LOCATED WITHIN 10 FEET (3048 MM) OF THE
 OPENING.
  
 4. INTAKE OPENINGS ON STRUCTURES IN FLOOD HAZARD AREAS
 SHALL BE AT OR ABOVE THE ELEVATION REQUIRED BY SECTION
 1612.4 OF THE FLORIDA BUILDING CODE, BUILDING FOR
 UTILITIES AND ATTENDANT EQUIPMENT.
  
 401.4.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET (3048 MM)
 HORIZONTALLY FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT
 SOURCE, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS, EXCEPT
 AS OTHERWISE SPECIFIED IN THIS CODE. FRESH AIR INTAKES
 SHALL NOT BE LOCATED CLOSER THAN 10 FEET (3048 MM) FROM
 ANY CHIMNEY OR VENT OUTLET, OR SANITARY SEWER VENT
 OUTLET.
  
 THE EXHAUST FROM A BATHROOM OR KITCHEN IN A RESIDENTIAL
 DWELLING SHALL NOT BE CONSIDERED TO BE A HAZARDOUS OR
 NOXIOUS CONTAMINANT.
  
 401.5 INTAKE OPENING PROTECTION.
 AIR INTAKE OPENINGS THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR
 GRILLES. OPENINGS IN LOUVERS, GRILLES AND SCREENS SHALL
 BE SIZED IN ACCORDANCE WITH TABLE 401.5, AND SHALL BE
 PROTECTED AGAINST LOCAL WEATHER CONDITIONS. LOUVERS
 THAT PROTECT AIR INTAKE OPENINGS IN STRUCTURES LOCATED
 IN HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA 550.
 OUTDOOR AIR INTAKE OPENINGS LOCATED IN EXTERIOR WALLS
 SHALL MEET THE PROVISIONS FOR EXTERIOR WALL OPENING
 PROTECTIVES IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 403.2 OUTDOOR AIR REQUIRED.
 THE MINIMUM OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 403.3. VENTILATION SUPPLY
 SYSTEMS SHALL BE DESIGNED TO DELIVER THE REQUIRED RATE
 OF OUTDOOR AIRFLOW TO THE BREATHING ZONE WITHIN EACH
 OCCUPIABLE SPACE.
  
 403.4 EXHAUST VENTILATION.
 EXHAUST AIRFLOW RATE SHALL BE PROVIDED IN ACCORDANCE
 WITH THE REQUIREMENTS IN TABLE 403.3. EXHAUST MAKEUP
 AIR SHALL BE PERMITTED TO BE ANY COMBINATION OF OUTDOOR
 AIR, RECIRCULATED AIR AND TRANSFER AIR, EXCEPT AS
 LIMITED IN ACCORDANCE WITH SECTION 403.2.
  
  
 601.4 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
  
  
  