| 2014-10-29 15:31:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | SHEET LS1.01 IDENTIFIES MULTIPLE EXITS; HOWEVER, THE |
| | REMOTENESS OF THE EXITS DO NOT COMPLY WITH THE |
| | REQUIRMENTS OF NFPA 101, CHAPTER 7, 7.5.1.3.2. |
| | |
| | THE EXIT LOCATED BY THE STAGE AND THROUGH THE STUDY |
| | ROOM, DOES NOT MEET THE CAPACITY OR EXIT REQUIREMENTS |
| | NECESSARY TO FUNCTION AS AN EXIT FOR THE OCCUPANCY. THE |
| | EXIT PATH CAN NOT PASS THROUGH THE STAGE AND STUDY |
| | ROOM; 7.5.2. IMPEDMENTS TO EGRESS. |
| | |
| | PROVIDE FOR EMERGENCY LIGHTING THAT ILLUMINATES THE |
| | EXIT PATH LEADING TO THE EXITS. |
| | |
| | FOR ASSEMBLY WITH AN OCCUPANT LOAD OF 100 OR MORE |
| | PERSONS (50 PERSONS PER THE FLORIDA BUILDING CODE), |
| | PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE |
| | THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED |
| | THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A |
| | SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS |
| | PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO |
| | LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO |
| | REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN |
| | LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK |
| | TO BE EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW |
| | (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN |
| | STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A |
| | KEYED LOCK. |