Plan Review Notes
Plan Review Notes For Permit 14100745
Permit Number 14100745
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-10-29 15:31:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET LS1.01 IDENTIFIES MULTIPLE EXITS; HOWEVER, THE
 REMOTENESS OF THE EXITS DO NOT COMPLY WITH THE
 REQUIRMENTS OF NFPA 101, CHAPTER 7, 7.5.1.3.2.
  
 THE EXIT LOCATED BY THE STAGE AND THROUGH THE STUDY
 ROOM, DOES NOT MEET THE CAPACITY OR EXIT REQUIREMENTS
 NECESSARY TO FUNCTION AS AN EXIT FOR THE OCCUPANCY. THE
 EXIT PATH CAN NOT PASS THROUGH THE STAGE AND STUDY
 ROOM; 7.5.2. IMPEDMENTS TO EGRESS.
  
 PROVIDE FOR EMERGENCY LIGHTING THAT ILLUMINATES THE
 EXIT PATH LEADING TO THE EXITS.
  
 FOR ASSEMBLY WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS (50 PERSONS PER THE FLORIDA BUILDING CODE),
 PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE
 THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED
 THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A
 SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS
 PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO
 LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO
 REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN
 LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK
 TO BE EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN
 STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A
 KEYED LOCK.