| 2014-10-29 10:33:12 | ENGINEERING DEPT COMMENTS |
| | 1. PLEASE SUBMIT APPLICATIONS FOR A DEVELOPMENT PERMIT |
| | AND RIGHT-OF-WAY PERMIT FROM THE ENGINEERING |
| | DEPARTMENT. APPLICATION FORMS CAN BE FOUND AT |
| | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ |
| | (SECTIONS 2-421 AND 78-432, CODE OF ORDINANCES) |
| | |
| | 2. PLEASE CLARIFY WHICH VERTICAL DATUM HAS BEEN USED |
| | FOR THE PLANS. SECTION 78-9 OF THE CITY?S CODE OF |
| | ORDINANCES SPECIFIES NGVD 1929 AS THE OFFICIAL CITY |
| | VERTICAL DATUM. |
| | |
| | 3. CONSIDER USING A DOUBLE ROW OF SILT FENCE ALONG THE |
| | RIGHT-OF-WAY FOR THE STUB CANAL TO AS ADDITIONAL |
| | PROTECTION FOR THE CITY?S CANAL. |
| | |
| | 4. PLEASE SHOW THE EXISTING DRAINAGE PIPES AND MANHOLES |
| | ON THE PLANS. SKETCH AND LEGAL FOR DRAINAGE EASEMENT |
| | WILL NEED TO BE PREPARED AND SUBMITTED TO WPB PUBLIC |
| | WORKS DEPARTMENT. PLEASE CONTACT KELLY CRANFORD |
| | ([email protected] OR 561-494-1098) TO GET COPIES OF |
| | THE EXISTING UTILITY INFORMATION. |
| | |
| | 5. REVISE THE PLANS TO SHOW THE EASEMENTS RESERVED |
| | UNDER RESOLUTION 139-72 (15 FT DRAINAGE EASEMENT 6 FT |
| | UTILITY EASEMENT). |
| | |
| | 6. WILL THE PERVIOUS CONCRETE PROPOSED TO BE USED ON |
| | THE PARKING LOT BE ABLE TO SUPPORT WEIGHT OF FIRE AND |
| | PARAMEDICAL EQUIPMENT (32 TONS)? |
| | |
| | 7. THE DUMPSTER WILL BE SERVICED BY OUR REFUSE TRUCKS, |
| | WHICH HAVE A WEIGHT OF APPROXIMATELY 20,000 POUNDS PER |
| | AXLE. THE PERVIOUS AREA, WHICH IS PROPOSED WHERE THE |
| | TRUCKS FRONT TIRES WOULD BE LOCATED WHILE THE TRUCK |
| | EMPTIES THE DUMPSTER, IS NOT CAPABLE OF SUPPORTING THE |
| | WEIGHT OF THE TRUCK. REVISE THE PLANS TO INCLUDE HEAVY |
| | TRAFFIC RATED ASPHALT OF CONCRETE IN THIS AREA. |
| | |
| | 8. CORRECT THE PROJECT ADDRESS ON THE LANDSCAPE PLANS |
| | TO 1101 CHARLES STREET INSTEAD OF 1001. |
| | |
| | 9. THE PARKING ON CHARLES STREET DOES NOT MEET THE |
| | REQUIREMENTS OF SECTION 94-313(2) WHICH REQUIRES A |
| | MINIMUM CORNER CLEAR DISTANCE OF 50 FEET. THE EXISTING |
| | PARKING LOT CONFIGURATION WAS APPROVED ONLY FOR |
| | TEMPORARY PARKING. REVISE THE SITE LAYOUT TO MEET THE |
| | CITY?S CODE OF ORDINANCES. |
| | |
| | 10. VERIFY THAT THE PROPOSED SIZE AND QUANTITY OF TRASH |
| | BINS IS APPROPRIATE FOR THE WASTE YARDAGE ANTICIPATED |
| | TO BE GENERATED BY THE COMPLEX. |
| | |
| | 11. DETAILS OF THE STORMWATER, POTABLE WATER, SANITARY |
| | SEWER AND SANITATION DESIGN WILL BE REVIEWED AS PART OF |
| | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION. THE |
| | PROJECT IS WITHIN THE C-51 DRAINAGE BASIN WHICH HAS |
| | LIMITATIONS ON FILL AND IS ALSO WITHIN FLOOD ZONE A9. |
| | |
| | KELLY CRANFORD, PE |
| | LAND DEVELOPMENT ENGINEER |
| | ENGINEERING & PUBLIC WORKS DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | 561-494-1098 (OFFICE) |
| | |