| 2014-12-08 10:13:28 | 12/8/2014 |
| | PROJECT: IGLESIA SANCTUARY |
| | PERMIT#: 14100745 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FBC- 107.3.5.3. PROVIDE A DETAILED ELECTRICAL |
| | SERVICE RISER TO INCLUDE THE FOLLOWING: A GROUNDING |
| | ELECTRODE SYSTEM. ALL SERVICE DISCONNECTS, AND PANELS. |
| | ALL CONDUIT AND WIRE SIZES. |
| | |
| | 2) FBC- 107.3.5.3.IN ADDITION TO THE RISER DIAGRAM THE |
| | FOLLOWING IS REQUIERD TO BE INCLUDED ON THE ELECTRICAL |
| | PLANS: A COMPLETE DETAILED LOAD CALCULATION(S). CLEAR |
| | AND SPECIFIC PANEL DIRECTORIES. ALL CIRCUIT NUMBERS AS |
| | INDICATED ON THE PANEL DIRECTORIES SHOWN ON THE FLOOR |
| | PLAN |
| | |
| | 3) NEC 110.9. VERIFY THE ELECTRICAL SERVICE |
| | DISCONNECTING MEANS HAS A FAULT CURRENT RATING THAT IS |
| | SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT |
| | THAT MUST BE INTERRUPTED. |
| | |
| | 4) NEC 110.16, 110.22. PROVIDE SAFETY LABELING FOR ARC |
| | FLASH PROTECTION FOR THE PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. |
| | |
| | 5) NEC 440.14. DISCONNECTING MEANS SHALL BE LOCATED |
| | WITHIN SIGHT FROM AND READILY ACCESSIBLE FROM THE |
| | AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. THE |
| | DISCONNECTING MEANS SHALL BE PERMITTED TO BE INSTALLED |
| | ON OR WITHIN THE AIR-CONDITIONING OR REFRIGERATING |
| | EQUIPMENT. INDICATE THE LOCATION OF THE A/C EQUIPMENT |
| | ON THE PANS. |
| | |
| | 6) NEC 422.31. VERIFY THE WATER HEATER HAS THE REQUIRED |
| | ELECTRIC DISCONNECT. INDICATE THE LOCATION OF THE |
| | ELECTRICAL WATER HEATER AND ASSOCIATED DISCONNECT ON |
| | THE PLANS. |
| | |
| | 7) NEC 600.5. EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE OUTLET |
| | SUPPLIED BY A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES |
| | THAT SUPPLIES NO OTHER LOAD. |
| | |
| | 8) NEC 314.27(C ). BOXES LISTED SPECIFICALLY FOR THIS |
| | APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED IN |
| | THE FLOOR. PROVIDE MANUFACTURER'S SPECIFICATION DATA |
| | SHEETS FOR THE OUTLETS LOCATED IN THE STAGE FLOOR. |
| | |
| | 9) NEC 422.52. ELECTRIC DRINKING FOUNTAINS SHALL BE |
| | PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER |
| | PROTECTION. . INDICATE ON THE PLAN |
| | |
| | 10) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM, |
| | SECURITY, CCTV, NETWORK, DATA, COMMUNICATION, SITE |
| | LIGHTING, AND GENERATORS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |