2014-11-21 17:44:042207 DOCK ST. PERMIT # 14100745.DOC
  
 BUILDING PLAN REVIEW
 PERMIT: 12030383
 ADD: 1101 CHARLES ST
 CONT: CANCIO BUILDERS, INC
 TEL: (772)263-0169
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: FRI. NOV. 21/ 2014
 ACTION: DENIED
  
 1A) THIS NEW PROPOSED STRUCTURE IS LOCATED IN AN A-9
 FLOOD ZONE. PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 1612.3. FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED. PLEASE REVIEW CITY ORDINANCE FOR THE CITY
 REQUIREMENTS REQUIRE AN ADDITIONAL 6 INCHES OF
 ELEVATION OR 13'-6" NGVD. PLEASE NOTE THE ARCHITECTURA
 PLANS INDICATE FINISH FLOOR OF 16.0 FT. THERE IS NO
 IDENTIFICATION IF THIS IS NGVD 29 OR NAVD 88?
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANT
 A/C PADS OR OTHER SLABS FOR GENERATORS
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 1B) PLEASE ALSO BE ADVISED OF THE FLOOD DESIGN CRITERIA
 FOUND IN SECTION 2010 FBC-B 1612.4 DESIGN AND
 CONSTRUCTION. THE DESIGN AND CONSTRUCTION OF BUILDINGS
 AND STRUCTURES LOCATED IN FLOOD HAZARD AREAS, INCLUDING
 FLOOD HAZARD AREAS SUBJECT TO HIGH-VELOCITY WAVE
 ACTION, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF ASCE 7
 AND WITH ASCE 24.
  
 1C) PLEASE PROVIDE CODE COMPLIANCE WITH FBC-B 1804.4
 (1-4). GRADING AND FILL IN FLOOD HAZARD AREAS. IN FLOOD
 HAZARD AREAS ESTABLISHED IN SECTION 1612.3, GRADING
 AND/OR FILL SHALL NOT BE APPROVED: SEE 1-4.
  
 1D) 1804.5 COMPACTED FILL MATERIAL. WHERE SHALLOW
 FOUNDATIONS WILL BEAR ON COMPACTED FILL MATERIAL, THE
 COMPACTED FILL SHALL COMPLY WITH THE PROVISIONS OF AN
 APPROVED GEOTECHNICAL REPORT, AS SET FORTH IN SECTION
 1803.
  
 2) PLEASE PROVIDE SOILS REPORT: FBC-B 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
 1803.5 INVESTIGATED CONDITIONS.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED AS
 INDICATED IN SECTIONS 1803.5.1 THROUGH 1803.5.12.
  
 3A) SHEET A.02 THE SITE PLANS INDICATE 2 BUILDINGS WITH
 15 FEET BETWEEN THE 2 BUILDINGS, PLEASE PROVIDE EITHER
 AN ASSUMED PROPERTY LINE BETWEEN THE 2 BUILDINGS
 SHOWING COMPLIANCE WITH FBC-B TABLE705.8 ALLOWABLE
 OPENINGS FOR BOTH BUILDINGS OR COMPLIANCE WITH FBC-B
 503.1.2 .
  
 3B) SHEET A.02 THE SITE PLAN SHOWS 15 FEET BETWEEN
 BUILDINGS PLEASE PROVIDE AN ASSUMED PROPERTY LINE TO
 SHOW COMPLIANCE WITH TABLE 602 FOR TYPE III-B
 CONSTRUCTION IN HOUR RESISTANCE RATING FOR EXTERIOR
 BEARING WALLS.
  
 4A) PLEASE PROVIDE COMPLIANCE WITH THE FLORIDA ENERGY
 CODE 103.2.1 CODE DEMONSTRATION FORMS. SEE TABLE
 103.2.1. 103.2.2.2 SIMULATED PERFORMANCE ALTERNATIVE,
 COMMERCIAL AND HIGH-RISE RESIDENTIAL.
 AN ACCURATELY COMPLETED COMMERICAL BUILDING FORM 506
 (GENERATED BY COMMISSION APPROVED SOFTWARE)
 DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR
 COMPLIANCE BY SECTION 506.
  
 4B) 103.2.2 DETAILS REQUIRED. CONSTRUCTION DOCUMENTS
 SHALL BE DRAWN TO SCALE UPON SUITABLE MATERIAL. L.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED, AND SHOW IN SUFFICIENT DETAIL PERTINENT DATA
 AND FEATURES OF THE BUILDING, SYSTEMS AND EQUIPMENT AS
 HEREIN GOVERNED. DETAILS SHALL INCLUDE, BUT ARE NOT
 LIMITED TO, AS APPLICABLE, INSULATION MATERIALS AND
 THEIR R-VALUES; FENESTRATION U-FACTORS AND SHGCS;
 AREA-WEIGHTED U-FACTOR AND SHGC CALCULATIONS;
 MECHANICAL SYSTEM DESIGN CRITERIA; MECHANICAL AND
 SERVICE WATER HEATING SYSTEM AND EQUIPMENT TYPES, SIZES
 AND EFFICIENCIES; ECONOMIZER DESCRIPTION; EQUIPMENT AND
 SYSTEMS CONTROLS; FAN MOTOR HORSEPOWER (HP) AND
 CONTROLS; DUCT SEALING, DUCT AND PIPE INSULATION AND
 LOCATION; LIGHTING FIXTURE SCHEDULE WITH WATTAGE AND
 CONTROL NARRATIVE; AND AIR SEALING DETAILS.
  
 5) SHEET LS1.01 INDICATES THE USE OF EXIT LIGHTS BUT
 THE PLANS DOES NOT SHOW EMERGENCY LIGHTING, 006.1.6
 SOURCES OF ILLUMINATION.
 1006.1.6.1 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 FROM A SOURCE OF REASONABLY ENSURED RELIABILITY.
 1006.1.6.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER
 TYPES OF PORTABLE LAMPS OR LANTERNS SHALL NOT BE USED
 FOR PRIMARY ILLUMINATION OF MEANS OF EGRESS.
 BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO
 BE USED AS AN EMERGENCY SOURCE TO THE EXTENT PERMITTED
 UNDER SECTION 1006.2.3.4.
  
 6) LS1.01 ROOM 103 HAS A DASHED LINE, WHAT APPEARS TO
 BE A FOLDING WALL PARTITION, PLEASE PROVIDE THE
 MANUFACTURERS SPEC FOR THE WEIGHT AND HOW THIS WILL BE
 ATTACHED TO THE LIGHT TRUSS FRAMING SYSTEM, THESE
 TRUSSES HAVE TO A HEAVIER BOTTOM CHORD LIVE LOAD
 SECTION FBC-B TABLE 1607.1. SHEET A-2.01 SHOWS A
 CATHEDRAL CEILING? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7) SHEET A-1.01 THE ROOM FINISH SCHEDULE GYPSUM BOARD
 IN RESTROOMS TO BE MOISTURE RESISTANT; PLEASE REVIEW
 2010 FBC-B 2509.1 WET AREAS.
 SHOWERS AND PUBLIC TOILET WALLS SHALL CONFORM TO
 SECTIONS 1210.2 AND 1210.3.
  
 8) SHEET A-3.02 THIS SHEET IS LABELED ROOF FRAMING PLAN
 WHICH ONLY SHOWS THE FILLED CELL LAYOUT. THE ROOF TRUSS
 FRAMING SYSTEM IS PART OF THE MAIN WIND FORCE RESISTING
 SYSTEM (MWFRS) THE DESIGNER OF RECORD IS TO PROVIDE THE
 MAGNITUDE OF LOADS TO BE RESISTED FOR UPLIFT, GRAVITY
 AND F1/ F2 HORIZONTAL LOADS. 1609.6.4.1. THIS SHEET
 DOES NOT PROVIDE WHAT THE DESIGN CRITERIA FOR THE WIND
 DESIGN.
  
 FBC-B2303.4.2 TRUSS PLACEMENT DIAGRAM. THE TRUSS
 MANUFACTURER SHALL PROVIDE A TRUSS PLACEMENT DIAGRAM
 THAT IDENTIFIES THE PROPOSED LOCATION FOR EACH
 INDIVIDUALLY DESIGNATED TRUSS AND REFERENCES THE
 CORRESPONDING TRUSS DESIGN DRAWING. THE TRUSS PLACEMENT
 DIAGRAM SHALL BE PROVIDED AS PART OF THE TRUSS
 SUBMITTAL PACKAGE, AND WITH THE SHIPMENT OF TRUSSES
 DELIVERED TO THE JOB SITE. TRUSS PLACEMENT DIAGRAMS
 THAT SERVE ONLY AS A GUIDE FOR INSTALLATION AND DO NOT
 DEVIATE FROM THE PERMIT SUBMITTAL DRAWINGS SHALL NOT BE
 REQUIRED TO BEAR THE SEAL OR SIGNATURE OF THE TRUSS
 DESIGNER.
  
 9A) SHEET S-9 SHOWS THE USE OF INSULATING CONCRETE
 FORMS (ICF) , PLEASE PROVIDE THE MANUFACTURER
 SPECIFICATIONS FOR THE USE OF THIS PRODUCT INCLUDING
 THE LOADING, FACTORS, REINFORCING REBAR DETAILS AND
 LIMITATIONS OF USE. 2010 FBC-B 918.2 INSULATED CONCRETE
 FORM WALL. INSULATED CONCRETE FORM (ICF) WALL
 CONSTRUCTION FOR BUILDINGS SHALL BE IN ACCORDANCE WITH
 ACI 318.
  
 9B) NEITHER THE A SHEETS OR S SHEETS SHOW COMPLIANCE
 WITH 2010 FBC-B 2603.8 PROTECTION AGAINST TERMITES. IN
 FLORIDA, EXTRUDED AND EXPANDED POLYSTYRENE,
 POLYISOCYANURATE AND OTHER FOAM PLASTICS SHALL NOT BE
 INSTALLED ON THE EXTERIOR FACE OR UNDER INTERIOR OR
 EXTERIOR FOUNDATION WALLS OR SLAB FOUNDATIONS LOCATED
 BELOW GRADE. THE CLEARANCE BETWEEN FOAM PLASTICS
 INSTALLED ABOVE GRADE AND EXPOSED EARTH SHALL BE AT
 LEAST 6 INCHES (152 MM).
  
 PLEASE SHOW FOOTER DEPTH, GRADE, THE 6 INCHES CLEAR
 AREA BEFORE THE START OF ICF BLOCKS OR WALL PANELS. THE
 6 INCHES IS TO VISSUALLY SEE TERMITE TUNNELS ON THE
 EXTERIOR OF THE BUILDING.
  
 9C) PLEASE PROVIDE FROM THE ICF MANUFACTURER, THEIR
 PRODUCT DESIGN FOR FLASHING AROUND WINDOWS, AND BUCK
 ATTACHMENT DETAILS SINCE WILL BE PART OF THE DOCUMENTS
 THAT WILL NEED TO BE REVIEWED BY THE DESIGNER OF RECORD
 AND THEIR DESIGN. NOTE TTHE WIND LOADS REQUIRED FOR THE
 BUCKS TO MEET THE REQUIED DESIGN PRESSURES. 107.2.1.3.
 ADDIRTIONAL INFORMATION. 107.2.4 EXTERIOR WALL
 ENVELOPE. CONSTRUCTION DOCUMENTS FOR ALL BUILDINGS
 SHALL DESCRIBE THE
 EXTERIOR WALL ENVELOPE IN SUFFICIENT DETAIL TO
 DETERMINE COMPLIANCE WITH THIS CODE. THE CONSTRUCTION
 DOCUMENTS SHALL PROVIDE DETAILS OF THE EXTERIOR WALL
 ENVELOPE AS REQUIRED, INCLUDING FLASHING, INTERSECTIONS
 WITH DISSIMILAR MATERIALS, CORNERS, END DETAILS,
 CONTROL JOINTS, INTERSECTIONS AT ROOF, EAVES OR
 PARAPETS, MEANS OF DRAINAGE, WATER-RESISTIVE MEMBRANE
 AND DETAILS AROUND OPENINGS. THE CONSTRUCTION DOCUMENTS
 SHALL INCLUDE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING
 DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING
 DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS
 MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL
 ENVELOPE. THE SUPPORTING DOCUMENTATION SHALL FULLY
 DESCRIBE THE EXTERIOR
 WALL SYSTEM WHICH WAS TESTED, WHERE APPLICABLE, AS WELL
 AS THE TEST PROCEDURE USED.
  
 9D) THE PLANS DO NOT INDICATE HOW THE INTERIOR OF THE
 STRUCTURE WILL BE FINISHED, SHEET A1.01, NOTE THE ROOM
 FINISH SCHEDULE STATES DRYWALL, NO THICKNESS HAS BEEN
 PROVIDED NOR COMPLIANCE WITH FBC-B 2603.4 THERMAL
 BARRIER.
  
 10A) SHEET A1.01 ROOM FINISH SCHEDULE DOES NOT INDICATE
 HOW THE BOTTOM CHORD OF THE TRUSSES IS TO ACT AS A
 DIAPHRAM OR IF LATERAL BRACING IS TO BE USED,
 EXSPECIALLY IN THE ROOMS WITH DROPPED CEILINGS. 2010
 FBC-B 303.4.1.2 PERMANENT INDIVIDUAL TRUSS MEMBER
 RESTRAINT.
 WHERE PERMANENT RESTRAINT OF TRUSS MEMBERS IS REQUIRED
 ON THE TRUSS DESIGN DRAWINGS, IT SHALL BE ACCOMPLISHED
 BY ONE OF THE FOLLOWING METHODS: 1-3.
  
 10B) SHEET SHOWS THE USE OF SCISSOR OR SLOPED CEILING
 TRUSSES, NO INFORMATION HAS BEEN PROVIDED WHERE THE
 ROOF INSULATION IS GOING TO BE LOCATED, NOR TYPE OF
 INSULATION. ENERGY 502.2.1.2.
  
 11) DISCREPANCY IN PLANS, A2.01 VERSES A3.02 SECTION
 A/A IS THROUGH THE ROOF WHERE IT GOES TO A PEEK WHICH
 WILL BE APPROX. 2 FT. HIGHER THAN INDICATES WITH THIS
 TRUSS SHOWN . THE FLAT TRUSS AS ILLUSTRATED WILL BE AT
 THE STEPLE/ BELL TOWER. NOTE NO DETAILS, FRAMING WERE
 SUBMITTED FORTHIS AREA NOR FLASHING OF THE FLOOR DECK
 OF THE STEPLE/ BELL TOWER. WILL NEED TO SHOW ANCHORAGE
 TO THE MWFRS TRUSSES. 107.2.1.3.
  
 12) THE DESIGNER OF RECORD HAS PROVIDED A LIST OF
 PRODUCT APPROVALS, PLEASE PRINT (2) COPIES OF THE
 PRODUCT APPROVALS, UNTIL THE PRODUCT APPROVALS ARE
 PRINTED, THE DESIGNER OF RECORD CIRCLES TYPE OF WINDOW,
 DOOR AND OR TYPE OF GLAZING AND ANCHORING, THE
 APPROVALS CAN NOT BE REVIEWED, THERE ARE TO MANY
 UNKNOWNS TO BE ABLE TO SHOW CODE COMPLIANCE.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. L.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  