| 2014-11-26 11:39:29 | RESIDENTIAL (R3) SCREEN ENCLOSURE, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PERSON RESPONSIBLE FOR THE DESIGN TO PROVIDE THE |
| | NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 2- PROVIDE DETAILS FOR THE 5" SUPPER GUTTER |
| | CONNECTIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 3- THE ALLOWABLE SPAN FOR PURLINS TABLE 102F SUBMITTED |
| | IS 4'-10". THIS DOESN'T REFLECT SPAN SHOWN ON PLANS. |
| | REVISE AS REQUIRED TO COMPLY. SEC. R301.1 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- REVISE ALLOWABLE POST/COLUMN SPAN CIRCLED WITH RED |
| | INK ON TABLE 103F SUBMITTED. THE SPACING FOR SIDE WALL |
| | POSTS IS NOT 6'-6". SEE PLANS AND REVISE AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- REVISE ALLOWABLE SPAN FOR GIRTS OR CHAIR RAILS |
| | CIRCLED WITH RED INK ON TABLE 204F SUBMITTED. THE |
| | SPACING IS NOT 4'-0". SEE PLANS AND REVISE AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 6- ALLOWABLE POST HEIGHT FOR 3/8" CONCRETE FASTENERS ON |
| | TABLE 105 SUBMITTED IS 8.3'. THIS DOESN'T REFLECT POST |
| | HEIGHT IN PLANS. REVISE AS REQUIRED TO COMPLY. SEC. |
| | R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 7- SPECIFY SIZE OF EXISTING FOOTING. SEC. R301.1 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | 8- PROVIDE ONLY THE DETAILS AND TABLES THAT APPLY TO |
| | THIS PROJECT TO AVOID CONFLICTS OF CONFUSION. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | |