Notes
Date Text
2014-11-02 03:21:471) RM. 355 - THE TOILET ROOM SHALL COMPLY WITH THE 2010
 FL. ACCESSIBILITY CODE SECS.213.2 , 603 & 305. SHOW THE
 REQUIRED TURNING SPACE WITHIN THE TOILET ROOM IN
 ACCORDANCE W/ SEC.304.3.OF 2010 FAC. SHOW THE REQUIRED
 CLEAR FLOOR SPACE FOR THE WATER CLOSET AND THE
 LAVATORY. THE CLEARANCE FOR THE WATER CLOSET SHALL
 COMPLY W/FAC SEC.604.3.
 2) BACKING FOR THE GRSB BARS SHALL BE INSTALLED PER FAC
 SEC. 604.5.
 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATION
 SHEETS AND INSTALLATION MANUAL PER THE WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 4) SHOCK ARRESTORS SHALL BE INSTALLED ON THE WATER
 LINES TO THE REFRIGERATORS PER 2010 FL. PLUMBING CODE
 SEC.604.9.
  