| Plan Review Notes For Permit 14100698 |
| Permit Number |
14100698 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-11-02 03:21:47 | 1) RM. 355 - THE TOILET ROOM SHALL COMPLY WITH THE 2010 | | | FL. ACCESSIBILITY CODE SECS.213.2 , 603 & 305. SHOW THE | | | REQUIRED TURNING SPACE WITHIN THE TOILET ROOM IN | | | ACCORDANCE W/ SEC.304.3.OF 2010 FAC. SHOW THE REQUIRED | | | CLEAR FLOOR SPACE FOR THE WATER CLOSET AND THE | | | LAVATORY. THE CLEARANCE FOR THE WATER CLOSET SHALL | | | COMPLY W/FAC SEC.604.3. | | | 2) BACKING FOR THE GRSB BARS SHALL BE INSTALLED PER FAC | | | SEC. 604.5. | | | 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATION | | | SHEETS AND INSTALLATION MANUAL PER THE WPB AMEND. TO | | | 2010 FBC SEC. 107.2.1. | | | 4) SHOCK ARRESTORS SHALL BE INSTALLED ON THE WATER | | | LINES TO THE REFRIGERATORS PER 2010 FL. PLUMBING CODE | | | SEC.604.9. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|